American Power Conversion PD80KG6FK1-M manual How to connect contacts to the PDU monitoring unit

Models: PD80KG6FK1-M PD80KF6FK1-M PD80KL6FK1-M

1 92
Download 92 pages 35.21 Kb
Page 72
Image 72

Customizing and Updating the PDU

How to connect contacts to the PDU monitoring unit.

1.Choose one or more contact numbers on the User/EPO contacts port on the user connection plate to which you will connect the contacts. The user connection plate connects to the PDU monitoring unit.

2.From the PDU display interface:

a.Press the ESC or ENTER key to go to the top-level menu screen.

b.Select Contacts on the top-level menu screen, and press the ENTER key.

Load-Meter Alarms

Volt-Meter Panel

Contacts Config

Breakers Help

c.Select Contact Inputs (or Relay Outputs) and press ENTER to display the contact inputs (or relay outputs) screen.

>Contact Inputs

>Relay Outputs

>Alarm Relay Map

d. Select Contact In and press the ENTER key to select the number of the contacts you are connecting. The continue arrow will appear next to the contact number.

Contact In:01of04

Name:User Contact 1

Normal: Open

Status: Closed

e. Press the Up or Down arrow key to select the appropriate contact number, and press the

ENTER key.

f.Press the Down arrow key to enter a unique Name for the contact and to configure the Normal state of the contact (Open or Closed). The default Normal state is Open. Press the ENTER key to select the item to configure.

You will be prompted for your password to configure these items.

Note

3.Connect contact wires (300V-rated cabling required) to the User Contacts terminal block on the user connection plate. You will need a 2.5-millimeter standard screwdriver.

4.Run the wires from the user connection plate to your contact’s location.

Ensure that wires are properly retained and away from high voltage lines and breakers.

Warning

64

80kW InfraStruXure PDU—Operation and Configuration

Page 72
Image 72
American Power Conversion PD80KG6FK1-M, PD80KF6FK1-M, PD80KL6FK1-M manual How to connect contacts to the PDU monitoring unit