American Power Conversion PD80KG6FK1-M, PD80KF6FK1-M, PD80KL6FK1-M How to Ensure Total Power Off

Models: PD80KG6FK1-M PD80KF6FK1-M PD80KL6FK1-M

1 92
Download 92 pages 35.21 Kb
Page 45
Image 45

How to Ensure Total Power Off

1.Command the UPS to turn off power to the load:

a.Press the ESC key at the top-level status screen to open the top-level menu and have access to eight submenus.

b.Select Control, and press the ENTER key.

c.Select Turn Load Off from the Control menu, and press the ENTER key.

Top-Level Menu

 

 

 

 

 

 

Control

Logging

 

 

Status

Display

 

 

Setup

Diags

 

 

Accessories

Help

 

 

 

 

Control Menu

UPS Into Bypass

Do Self Test

Simulate Power Fail

Graceful Reboot

Graceful Turn Off

Start Runtime Cal

Turn Load Off

d.On the next screen: select Yes, UPS Load OFF, and press the ENTER key.

Confirmation Screen

Confirm

Yes, UPS Load OFF

No, Abort

The Load On LED turns off and the interface displays the following two screens:

UPS has been

commanded to turn load power off...

UPS load is off

Press any key...

2.Set the UPS System Enable switch to the OFF position.

80kW InfraStruXure PDU—Operation and Configuration

37

Page 45
Image 45
American Power Conversion PD80KG6FK1-M How to Ensure Total Power Off, Set the UPS System Enable switch to the OFF position