How to Return from Maintenance Bypass Operation

 

Select Help from the top-level menu screen on the PDU display interface and select the

 

second help topic, Returning from PDU Maintenance Bypass, or follow the

Note

procedure below:

 

1. Close (turn ON) the Q1 circuit breaker on the PDU.

2. If applicable, close (turn ON) the PDU Q10 Bypass Input (B) switch.

3. Close (turn ON) the XR Battery Enclosure DC Disconnect circuit breaker.

34

80kW InfraStruXure PDU—Operation and Configuration