System Operation

4.Ensure that all battery units are pushed all the way into the XR Battery Enclosures and locked into position.

5. Set the XR Battery Enclosure DC Disconnect circuit breaker to ON.

6. Set the UPS System Enable switch to ON

When the System Enable switch is placed in the ON position, the Startup screen appears on the display interface of the Symmetra PX UPS.

PowerView RM

Rev: 000 English

Please wait...

The top-level status screen appears on the display interface. This may take up to 30 seconds.

Fuel%

Load%

In 208V out000V 60Hz

Runtime: 1hr 2m

40

80kW InfraStruXure PDU—Operation and Configuration

Page 48
Image 48
American Power Conversion PD80KG6FK1-M, PD80KF6FK1-M, PD80KL6FK1-M manual PowerView RM Rev 000 English Please wait