Installing an NXD-700Vi into an (optional) Rack Mount Kit (NXA-RK7)

The NXA-RK7 is a 19" (48.3 cm) wide metal rack-mount (with black matte finish) measuring 4 rack units high.

1.Remove the Faceplate/Trim Ring assembly from the main NXD-700Vi unit.

2.Thread the incoming power, RJ-45 audio/video, Ethernet, and USB wiring (from their terminal sources) through the surface opening, leaving enough slack in the wiring to accommodate any re-positioning of the panel.

3.Connect all data and power wiring connectors to their corresponding locations along the left side of the (un-powered) NXD touch panel.

Verify that the terminal end of the power cable is not connected to the a power supply before plugging in the 2-pin power connector.

The USB connectors can be from a either a USB extension cable, or a wireless USB RF transmitter.

4.Test the incoming wiring by connecting the panel connections to their terminal locations and applying power. Verify that the panel is receiving power and functioning properly to prevent repetition of the installation.

5.Disconnect the terminal end of the power cable from the connected power supply.

Don’t disconnect the connectors from the touch panel. The unit must be installed with the necessary connectors before being inserted into the equipment rack.

6.Carefully insert the NXD-700Vi panel into the NXA-RK7.

7.Secure the panel to the NXA-RK7 mount by first inserting and then tightening the four #4-40 screws.

8.Insert the NXA-RK7 (with connected NXD unit) into the equipment rack, making sure to align the screw holes along the sides on the NXA-RK7 with the holes in the equipment rack.

9.Use a grounded Phillips-head screwdriver to secure the NXA-RK7 to the equipment rack using #10-32 screws (included).

10.Place the Faceplate/Trim Ring assembly back onto the main NXD unit. Make sure to align the Microphone, Light, and PIR Motion sensor locations to their respective openings on the front faceplate/bezel.

11.Reconnect the terminal RJ-45 audio/video, Ethernet, and USB wiring to their respective terminal locations on either the NXA-AVB/ETHERNET Breakout Box, Ethernet port, or NetLinx Master.

12.Reconnect the terminal power connector on the 12 VDC-compliant power supply and apply power.