Balcar R410A service manual Drain-up, Connection of the drain hose, Check of water drain, 109

Models: R410A

1 109
Download 109 pages 54.47 Kb
Page 33
Image 33
Drain-up

Drain-up

If down-slope cannot be set on a drain pipe, drain-up is possible.

Set the height of drain pipe 550mm or less from the bottom face of the indoor unit.

Pull out the drain pipe from connecting port of the drain pipe of the indoor unit by 100mm or shorter, and stand up it vertically.

After standing up it vertically, arrange immediately so that it is set with down-slope.

RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E

100mm or

-up: 550mm or less

Standing

shorter

 

Indoor unit

 

Connection of the drain hose

 

As long as possible (Approx. 100mm)

• Insert the drain hose completely into

 

the connecting port of the drain pan.

 

 

VP 30

 

 

 

VP 30

 

 

 

VP 30

 

 

 

 

 

 

 

 

• Apply thermal insulation surely to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

drain hose with socket thermal insulation seal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VP 30 or more

Downward grading

 

 

 

 

 

 

 

 

1/100 or more

Extended ventilating pipe

Check of water drain

After drain pipe work, check that water is drained and there is no water leak from pipe connection portion. In this time, also check there is no trouble of motor sound of the drain pump. Be sure also to perform this check when installing the unit in heating time.

After electric piping work

Before installing a panel, infuse water as shown in the following figure. By operating the unit in COOL mode, check that water is drained from the drain pipe and then check there is no water leak from the drain pipe.

Before electric piping work

Pull out the float switch connector (3P: Red) from

connector (CN34: Red) on P.C. board of the electric parts box. (In this time, be sure to check the power has been turned off.)

Connect 200V single-phase to R and S of the power supply terminal block. (Never apply 200V to

A , B , U1 , and U2 of the terminal block, otherwise it causes a trouble of P.C. board.

Infuse water followed to the figure below. (Water amount: 1500cc to 2000cc)

The drain pump automatically operates by power-on. Check that water is drained from the drain pipe and then check there is no water leak from the drain pipe.

After checking water drain and water leak, turn off the power, connect the float switch connector to the original position (CN34) of P.C. board, and then return the electric parts box to the original position.

Insert the end of hose

Service plate

up to the near of suction

 

port of drain pump.

 

200–240V ~ single-phase

R S

White

Black Red

Black

Pull out CN34 connector from P.C. board.

– 109 –

Page 33
Image 33
Balcar R410A service manual Drain-up, Connection of the drain hose, Check of water drain, After electric piping work, 109