RAV-SM561, 801CT-E

RAV-SM1101, 1401CT-E

Accessory parts and Parts to be procured locally

rAccessory parts

Part name

Q’ty

Shape

Usage

 

 

 

 

Owner’s Manual

1

 

 

 

 

Installation Manual

1

This manual

 

 

 

 

Installation pattern

1

Drawing-out port of

 

hanging bolt pipe

 

 

 

 

 

 

 

Thermal insulation

2

 

For thermal insulation of

pipe

 

pipe connecting section

 

 

 

 

 

 

Washer

4

M10 × Ø25

For holding down unit

 

 

 

 

Hose band

2

 

For connecting drain

 

pipe

 

 

 

 

 

 

 

<Separate sold parts>

Part name

Q’ty

Shape

Usage

Standard wired

1

 

Model

 

 

remote controller

 

 

RBC-AMT21E

Part name

Q’ty

Shape

Usage

Drain hose

1

 

For connecting drain pipe

Bushing

1

 

For protection of edge at

 

power taking-in port

 

 

 

Thermal insulator

1

 

For thermal insulation of drain

 

hose (10t × 200 × 200)

 

 

 

Thermal insulator

1

 

For upper pipe hole of indoor

of top plate

 

unit (6t × 130 × 160)

 

 

Banding band

2

 

For prevention of open of

 

drain hose thermal insulator

 

 

 

rParts to be procured locally

Connecting pipe (Liquid side)

(6.4mm (diam.), Nominal (diam.) 1/4” thick 0.8mm) RAV-SM561CT-E

(9.52mm (diam.), Nominal (diam.) 3/8” thick 0.8mm) RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E

Connecting pipe (Gas side)

(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm) RAV-SM561CT-E

(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm) RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E

Power supply cord

2.5mm² (H07RN-F or 245IEC66) (20m or less) 3.5mm² (AWG-12) (50m or less)

Connecting cable (indoor and outdoor cable) H07RN-F or 245IEC66 (1.5mm² or more)

Thermal insulation for refrigerant pipe

(10mm or more, thermal insulating foam polyethylene)

Thermal insulation for drain pipe (10mm or more, foam polyethylene)

Drain pipe (Outer 26mm (diam.)) (VP20)

Tapes