In case of installation to high ceiling

RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E

In case of installation to high ceiling

When the height of the ceiling to be installed exceeds 3.5m, adjustment of air volume is necessary. Set up the high ceiling.

• Set according to the basic operation procedure

(1 2 3 4 5 6 ).

Item code in Procedure specifies [5d].

Select [Set data] in Procedure from “List of installable ceiling height” in this Manual.

For the item code in Procedure 3, specify [5d].

For the set data in Procedure 4, select the setup data of static pressure outside of the machine to be set up from the table below.

(Exchange by wired remote controller)

Set data

 

 

 

 

 

0000

Standard (At shipment)

3.5m or less

 

 

 

0001

High static pressure 1

4.0m or less

 

 

 

To incorporate a filter sold separately

When mounting a filter sold separately, be sure to set up the tap exchange according to the type of filter.

In this case, also follow to the basic operation procedure (1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [5d].

For the set data in Procedure 4, select the setup data of filter to be incorporated from the table below.

Set data

 

 

 

 

 

0000

Standard filter (At shipment)

 

 

 

 

0001

Zeolite-3G deodorant filter

Filter sold

 

 

0003

High-efficiency filter (65%)

separately

0006

Deodorant filter

 

Ammonium filter

 

 

 

 

 

 

When using wireless remote controller

To exchange the static pressure, there is a method other than the abovementioned method by wired remote controller, which is to shift the short plug on the indoor microcomputer P.C. board as shown in the following table. Adopt this method in case of using a wireless remote controller, etc.

*However, after exchanging once, be careful to shift the short plug to the standard position (At shipment) in order to return to the standard setup (follow to E2PROM setup) though the setup for high static- pressure 1, high static-pressure 2, or low static- pressure can be arbitrarily performed.

It is necessary to rewrite data from the wired remote controller sold separately in the set data “0000”.

Select by exchange of short plug on indoor microcomputer P.C. board.

Short plug position

Set data

Filter sold separately

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

Standard filter (At shipment)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0001

Zeolite-3G deodorant filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0003

High-efficiency filter (65%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0006

Deodorant filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ammonium filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If selecting the set data 0006, do not discard the removed short plug, but ask the users to keep it.

Short plug position

(CN112, CN111, CN110 from the left)

– 139 –