(3) Installation of ceiling panel

The angle change of the flap is possible while the power supply is turned on. (Do not move forcibly the flap with hands. It may break the flap.)

1.For tentative hanging, insert the tentative hanging metal (stainless) inside of the ceiling panel into the square hole of the indoor unit. (Fig. 2)

Square hole of indoor unit

Push to remove

(5) Installation of adjust corner cap/suction grille

Install the adjust corner cap/suction grille in the reverse procedure of installation to the indoor unit.

• For this ceiling panel, as shown in the following figure, the

direction of the suction grille can be changed on customer’s

Pin

The ceiling panel has directional ability against the indoor unit. Direct the mark of refrigerant pipe at the ceiling panel corner toward the pipe side.

Holding the ceiling panel, remove it while pushing the tentative hanging metal toward the outside.

2.Match the mounting hole of the panel with the screw hole of the indoor unit.

3.Using the attached screws with washer, tighten 4 positions at corners of the suction port until the panel is fitted closely to the main unit. (Fig. 3)

4. Check the panel is fitted closely to the ceiling.

• In this time, check there is no clearance between the indoor unit

and the ceiling panel, and between the ceiling panel and the

Ceiling panel

ceiling surface. (Fig. 4)

 

 

 

Indoor unit

No clearance

 

 

 

Tentative hanging metal

(Fig. 2)

Corner of drain pipe

Square hole of indoor unit

Draining mark

demand when multiple indoor units are installed.

A.Installation of adjust corner cap

1.Hook the strap of the adjust corner cap surely to the pin on the ceiling panel.

2.Install the adjust corner cap to the ceiling panel, and fix it with the mounting screws. (accessory part)

B.Installation of suction grille

• To install the suction grille, follow to the reverse procedure of the

removal. This ceiling panel can be installed from anyone of 4

directions by turning the suction grille. Change the direction on

the customer’s demand or according to the direction matching of

the suction grille when multiple units are installed.

• When installing the suction grille, be sure not to pinch the

Install the adjust corner cap horizontally to the ceiling surface so that 3 hooks of the adjust corner cap are set in holes of the ceiling panel. And then fix it with the mounting screws (accessory part).

Hook hole of ceiling panel

 

 

 

Screw

Mark of

(Fig. 4)

Ceiling surface

Ceiling panel

(Fig. 3) with washer

refrigerant pipe

Tentative hanging metal

CAUTIONS

flap motor wiring connector.

• Be sure to attach a strap to prevent falling of the suction grille to

the ceiling panel.

(Fig. 8)

Hook of

– 167 –

• Tighten the screws securely because

• When there is a clearance between the

a trouble is caused as shown in the

ceiling surface and the ceiling panel

following figure if the screws are

even if the screws have been tightened,

incompletely tightened.

readjust height of the indoor unit.

Air leak

 

The height of the indoor unit can be adjusted from corner hole on the ceiling panel as the ceiling panel is installed if the adjustment does not affect the levelness of the indoor unit, drain pipe, etc.

fall-preventive strap

3. Others

Air leak

 

 

from ceiling

 

 

Generation

Dewing/water

Adjust so that there is

of dust

leak

no clearance.

(Fig. 5)

(Fig. 6)

After adjustment, be sure to tighten the mounting nut of the indoor unit securely.

Positions of suction grille hooks at shipment from the factory

 

 

* Although the suction grille can be installed from any

Drain pipe side

position of 4 corners, these positions are recommended.

of indoor unit

It is unnecessary to remove the suction grille in

 

 

(maintenance for the electric parts box of the indoor unit. )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A. Check after installation

 

Electric parts box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check again there is no clearance between the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe side of indoor unit

Wireless remote controller kit (sold separately)

(Fig. 9)

 

(4) Cabling of ceiling panel

1.

Open cover of the electric parts box.

2.

Connect the flap motor wiring connector out

 

of the ceiling panel to the connector 5P

Wiring explanation diagram

(For explanation, direction of the indoor unit is changed.)

Electric parts box cover

indoor unit and the ceiling panel, and between the ceiling panel and the ceiling surface.

*A clearance causes water leak or dewing.

Check the cables are connected surely.

*Incomplete connection causes a trouble such as the flap does not work.

(CN33: white) on P.C. board of the indoor unit.

Screws

Flap motor wiring connector

• Connect the connector surely because

the flap does not work if the connector

is not connected.

3. Mount cover of the electric parts box in the

reverse procedure of opening of the cover.

• Check whether the wiring connector is

pinched between the electric parts box

and the cover or not.

• Check whether the wiring connector is

pinched between the indoor unit and the

ceiling panel or not.

(3 positions)

CN33

Clamper

As shown in the figure, pass the clamping material through inside of the slit. After connection, store the connector section in the electric parts box.

(Fig. 7)

B. For wireless remote controller

Direction-free in 360˚

• For details of installation, refer to the Installation Manual attached to the wireless remote controller kit (sold separately).

After confirmation of the above items, hand a set of this manual, manuals for the indoor unit, manual for products sold separately, etc. to the customer. For cleaning of the filter, be sure to ask the maintenance professional.

EH99708701-(1) (EN)

RBC-U21PG (W)-E

Page 91
Image 91
Balcar R410A 167, Installation of adjust corner cap, Installation of suction grille, Check after installation