Balcar R410A service manual Installation of Outdoor Unit, <Obstacle also at the upper side>, 23

Models: R410A

1 109
Download 109 pages 54.47 Kb
Page 9
Image 9
<Obstacle also at the upper side>

3 SELECTION OF INSTALLATION

<Obstacle also at the upper side>

1000

1000 moreor

or more

 

Obstacles at both front and rear sides

Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit.

<Standard installation>

1. Single unit installation

1000150 or more or more

2. Serial installation of two or more units

 

 

200 or more

300

300

1000 moreor

or more

or more

 

RAV-SP1100, 1400AT-E

RAV-SM1100, 1400AT-E

Installation of Outdoor Unit

Before installation, check strength and horizontality of the base so that abnormal sound does not generate.

According to the following base diagram, fix the base firmly with the anchor bolts.

(Anchor bolt, nut: M10 x 4 pairs)

 

 

150

 

600

150

 

 

 

 

 

430

 

 

 

Drain hole

40

 

 

 

 

 

400

365

Knockout hole

Drain nipple mounting hole

 

 

 

 

Set the out margin of the anchor bolt to 15mm or less.

15 or less

In case of drainning through the drain hose, attach the following drain nipple and the waterproof rubber cap, and use the drain hose (Inner diam.: 16mm) sold on the market. And also seal the screws securely with silicone material, etc. so that water does not drop down. Some conditions may cause dewing or drip- ping of water.

Serial installation at front and rear sides

Open the upper side and both right and left sides. The height of obstacle at both front and rear sides should be lower than the height of the outdoor unit.

<Standard installation>

1000

300

1500

2000

200

or more

or more

or more

or more

or more

Drain nipple

Waterproof rubber cap

Knockout hole

Open

Waterproof rubber cap

Obstacles at both front and rear sides<Standard installation> Drain nipple

When there is a possibility of freezing of drain at the cold district or a snowfall area, be careful for drainage ability of drain. The drainage ability increases when a knockout hole on the base plate is opened. (Open the knockout hole to outside using a screwdriver, etc.)

– 23 –

Page 9
Image 9
Balcar R410A Installation of Outdoor Unit, <Obstacle also at the upper side>, Obstacles at both front and rear sides, 23