System Grounding Continued

Ungrounded Distribution System

With an ungrounded power distribution system it is possible to have a continuous current path to ground through the MOV devices. To avoid equipment damage, an isolation transformer with a grounded secondary is recommended.

Input Power Conditioning

Certain power line conditions must be avoided. An AC line reactor or an isolation transformer may be required for some power conditions.

If the feeder or branch circuit that provides power to the driver has permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer must be connected between the power factor correction capacitors and the driver.

If the feeder or branch circuit that provides power to the driver has power factor correction capacitors that are switched on line and off line, the capacitors must not be switched while the driver is connected to the AC power line. If the capacitors are switched on line while the driver is still connected to the AC power line, additional protection is required. TVSS (Transient Voltage Surge Suppressor) of the proper rating must be installed between the AC line reactor or an isolation transformer and the AC input to the driver.

Power Disconnect A power disconnect should be installed between the input power service and the driver for a fail–safe method to disconnect power. The driver will remain in a powered-up condition until all input power is removed from the driver and the internal bus voltage is depleted.

Protection Devices The driver must have a suitable input power protection device installed. Input and output wire size is based on the use of copper conductor wire rated at 75 ° C. Table 3-1 describes the wire size to be used for power connections and the ratings of the protection devices. Use the recommended circuit breaker or fuse types as follows:

Circuit Breaker: 1 phase, thermal magnetic.

Equal to GE type THQ or TEB for 115 VAC Time Delay Fuses: Buss LPN on 115 VAC or equivalent.

Recommended fuse sizes are based on the following:

UL 508C suggests a fuse size of four times the continuous output current of the driver.

Dual element, time delay fuses should be used to avoid nuisance trips due to inrush current when power is first applied.

MN1854

Receiving & Installation 3-3

Page 14
Image 14
Baldor mn1854 manual System Grounding Ungrounded Distribution System, Input Power Conditioning