Standby Current (can be changed at any time)

Setting the Standby current DIP switch to ON reduces motor current by 30% when the drive has not received a step pulse for 250 msec. Full current is restored when the next step pulse is received. Each drive can also be set to standby with the EA2 software command.

A 30% reduction in motor current during Standby correlates with an approximate 30% reduction in motor holding torque. Do not use Standby mode in applications where you need more than 70% of the motor’s torque to hold a load stationary.

Standby should not be used in applications where an encoder is used to perform end–of–move position maintenance.

Waveform (can be changed at any time) On Sinusoid, Off for 4% 3rd harmonic.

Step Type (can be changed at any time) Not Used.

Anti–Res(can be changed at any time) Not Used.

Power On Checks

When power is first applied, the “ON” LED will be green. With the keypad connected, the LCD display will briefly display the initialization screens.

Note: The LCD display may require contrast adjustment for better viewing. If the display cannot be seen, adjust the potentiometer in Figure 3-15 for best viewing.

Action

 

Display

Comments

 

 

 

 

 

 

Apply Power.

 

 

 

 

Power–up diagnostic display. No errors.

 

+0.0000

 

 

 

 

 

 

 

 

 

00000000

00000000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The motor should now be producing torque.

Action

 

 

Display

 

Comments

 

 

 

 

 

 

Select “RUN, JOG (F2)”.

 

 

 

 

Select either Low or High to Jog the

JOG AXIS +0.0000

 

 

 

motor position. Confirm proper motor

 

 

<LO>

HIGH

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

 

MN1854

Receiving & Installation 3-13

Page 24
Image 24