RS232/Keypad Installation Procedure: (optional keypad – LXKP)

Optional Remote Keypad Installation

The keypad may be remotely mounted and sealed to NEMA 4 specification by using the gasket and 6 ft (1.8m) cable included. The keypad assembly is complete with the screws and gasket required to mount it to an enclosure. The gasket has adhesive on one side that must be placed toward the enclosure.

Tools Required:

Center punch.

3/16" drill bit (for clearance mounting holes).

1/2" (12.7) and 1-1/2" (38.1) standard knockout punch.

(4) 6-32 nuts and washers (or M3.5 hardware).

Remote keypad mounting template. A tear out copy is provided at the end of this manual for your convenience.

Mounting Instructions: (see remote keypad mounting template)

1.Locate a flat mounting surface. Material should be sufficient thickness (14 gauge minimum).

2.Place the template on the mounting surface or mark the holes as shown.

3.Accurately center punch the 4 mounting holes (labeled E for SAE or M for metric) and the three large Cut–Out holes.

4.Drill four 3/16" holes (at E or M).

5.Make the three large Cut–Out holes using the punch manufacturers instructions.

6.Debur knockout and mounting holes making sure the panel stays clean and flat.

7.Apply the adhesive backed gasket to the enclosure.

8.Assemble the keypad to the panel. Non–conductive screws and washers should be used to electrically isolate the keypad from the enclosure.

Caution: To prevent keypad damage, be sure keypad mounting screws do not extend more than 0.2 (5) into keypad assembly.

Keypad

 

 

 

 

x GND N/C

x

+5VDC

 

 

T R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.Connect the keypad cable to the “Remote Cable” connector, Figure 3-4.

Figure 3-5 Keypad (Nullmodem) Connections

Standard Connections

 

Keypad

 

 

External +5VDC

 

 

 

 

 

 

 

 

+5VDC

Connections

LinStep+

 

x GND N/C

x

LinStep+

 

External

T R

 

 

RS232 / Keypad

 

 

 

RS232 / Keypad

P.S.

 

 

 

Connector

 

 

 

Connector

+5VDC

 

 

 

+5VDC

 

 

 

+5VDC

 

 

 

 

Rx

 

 

 

 

Rx

Tx

GND

 

 

 

Tx

GND

 

 

 

 

GND

Shld

 

 

 

 

Shld

Note: A 6ft (1.8m) cable is provided with the keypad. If a longer cable is to be used, an external +5VDC @ 500mA power supply is required.

3-6Receiving & Installation

MN1854

Page 17