Table 3-1 Wire Size and Protection Devices

Catalog Number

Incoming Power

Nominal Input

Continuous

Input

Input Fuse

Wire Gauge

Output

Breaker

Time

AWG

mm2

Voltage

Amps (RMS)

(A)

Delay (A)

(USA)

(Europe)

 

 

 

 

 

 

 

LX2P1A06

115V (1f)

6.0A

20

20

14

2.5

Note: All wire sizes are based on 75° C copper wire. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 25° C ambient, maximum continuous driver output current and no harmonic current.

Power Connections Power connections are shown in Figure 3-3.

Figure 3-3 115VAC Single Phase AC Power Connections

 

 

 

L1

Neutral

Earth

 

Alternate *

L1

 

 

 

 

 

 

 

 

 

Note 3 & 4

 

 

 

 

 

 

 

 

 

 

 

 

Fuse

 

 

Note 1

Note 1

* Circuit

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 2

Breaker

 

 

 

 

Note 5

 

* Components not provided with driver.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

Line

 

Neutral

 

Earth

 

 

 

 

 

 

 

 

 

 

 

1.

See “Protection Devices” described in this section.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.Metal conduit or shielded cable should be used. Connect

 

Baldor

conduits so the use of a Reactor or RC Device does not

 

LinStep+

interrupt EMI/RFI shielding.

 

3.

Use same gauge wire for Earth ground as is used for L and N.

 

 

 

(VDE (Germany) requires 10mm2 minimum, 6AWG). For CE

 

 

 

Compliance, connect Earth to the backplane of the enclosure.

 

 

4.

Reference EMC wiring in Section 8.

 

 

Power 110VAC

5.

GND is located on the motor terminal strip.

Earth Neutral Line RPack RPack

 

 

 

Connector location is shown in Figure 3-4.

3-4Receiving & Installation

MN1854

Page 15
Image 15