UL Required Fuses for Short Circuit Rating

UL requires R/C fuses, special purpose fuses (JFHR2) or semiconductor fuses rated 700VAC be used to obtain the short circuit current ratings required by UL.

 

Fuse Manufacturer

Fuse

Short Circuit Rating

Model Number

Bussman (300 KA A.I.C.)

Ferraz (200 KA A.I.C.)

Current Rating

Amperes

 

Catalog Number

Catalog Number

Amperes

 

 

 

 

 

 

 

MD9 to MD16

170M3110

6.6 URD 30 D08 A 0063

63

5,000

MD23 to MD30

170M3112

6.6 URD 30 D08 A 0100

100

5,000

MD44

170M3114

6.6 URD 30 D08 A 0160

160

5,000

MD59

170M3115

6.6 URD 30 D08 A 0200

200

5,000

MD72 to MD85

170M3116

6.6 URD 30 D08 A 0250

250

10,000

MD105 to MD146

170M3119

6.6 URD 30 D08 A 0400

400

10,000

MD174 to MD202

170M3121

6.6 URD 30 D08 A 0500

500

10,000

 

 

 

 

 

MD242

170M4114

6.6 URD 31 D08 A 0500

500

10,000

MD300

170M4114

6.6 URD 31 D08 A 0500

500

18,000

MD370

170M4116

6.6 URD 31 D08 A 0630

630

18,000

MD500

170M6113

6.6 URD 33 D08 A 0900

900

18,000

MD600

170M6113

6.6 URD 33 D08 A 0900

900

30,000

MD750

170M6116

6.6 URD 33 D08 A 1250

1250

30,000

MD900

170M6116

6.6 URD 33 D08 A 1250

1250

42,000

MD1100

170M6116

 

1500

42,000

MD1200

(2) 170M6116

 

(2) 1000

42,000

Main Input Contactor An IEC or NEMA rated contactor is recommended at the input power to the control. The soft–start control uses three pairs of SCR (silicon controlled rectifier) semiconductor devices that do not positively disconnect power. Figure 2-1 shows that the input contactor provides a positive disconnect.

 

Table 2-2 Connection Descriptions

Terminal

Description

 

L1, L2, L3

Input AC power terminals. Connect input isolated 3 phase supply (any phase to any terminal).

T1, T2, T3

Output Power Terminals. Connect an induction motor to these terminals. For correct motor rotation,

connection of these phases must correspond with the supply connections (L1, L2, L3).

 

 

 

X1, X2

Control Supply Input. The internal circuits require power from a 115VAC or 230VAC source (Table 2-3).

A selector switch is provided to select the voltage range of the source that is connected to this input.

 

 

 

 

Remote Start/Stop Input. A voltage present across these terminals will initiate a “Start”.

S1, S0

Removing the voltage from across these terminals will initiate a “Stop”.

 

Note that the factory setting is keypad Start/Stop.

 

 

 

Relay K1

Pins 11 and 12 are the

normally closed “Run” relay contacts.

Pins 11 and 14 are the

normally open “Run” relay contacts.

 

Relay K2

Pins 21 and 22 are the

normally closed “Top of Ramp” relay contacts.

Pins 21 and 24 are the

normally open “Top of Ramp” relay contacts.

 

MN850

Installation 2-5

Page 10
Image 10