Reversing Contactor For this mode, the Stop Time must be set to zero. Also, allow a minimum of 350 milli
seconds between the Forward and Reverse commands.
Figure 2-7 Motor Reversing Connection
To AC Input
|
|
|
|
| Forward |
|
|
| Reverse |
|
|
|
|
| Contacts |
|
| MI | Contacts |
To protect the control, be sure to add MOV protection. |
|
|
|
|
| ||||
Refer to Appendix D for additional information. |
|
|
|
|
|
| |||
115/230VAC |
|
|
|
|
|
|
| MI - Mechanical Interlock | |
Fuse | Neutral |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| X1 |
| L1 | L2 | L3 |
|
| Forward | R | F | X2 |
|
|
|
|
|
|
|
| S1 |
|
|
|
|
| |
|
| F |
|
|
| Baldor |
| ||
| Reverse |
| R | S0 |
|
|
| ||
|
| Note 1 |
|
|
| Digital |
| ||
|
| R | 14 |
|
|
| |||
|
|
|
|
|
| ||||
|
|
|
|
|
|
| |||
|
|
|
| 11 | K1 |
| Note 1: Add appropriately rated protective | ||
|
|
|
| 12 |
|
|
| ||
|
| F |
|
|
|
|
| ||
|
|
|
|
|
|
| device for AC relay (snubber) | ||
|
|
|
| 24 |
|
|
|
| |
|
|
|
|
| K2 is factory preset |
| or DC relay (diode). | ||
|
|
|
| 21 | K2 |
|
| ||
|
|
|
| as the •Top of Ramp" function. |
| ||||
|
|
|
| 22 |
|
| |||
* External hardware not provided with control. |
|
| T1 | T2 | T3 |
| |||
|
|
|
|
|
|
See Recommended Tightening Torques in Table
MN850 | Installation |