Title

P#

Parameter

 

Description

 

 

 

 

Advanced Current

P71

Contactor Delay (after start command)

Sets the delay time between the request to actuate K1 and the start

 

 

 

of firing the thyristors.

 

 

 

 

 

P72

Trip Sensitivity (1=fastest trip)

Unused

 

 

 

 

 

P73

Last Trip (Most Recent Trip)

P73 stores the most recent trip code for the most recent fault. Trip

 

 

 

code definitions are as follows:

 

 

 

0

Not Used

 

 

 

1

Phase Loss Fault. One or phases of the incoming three phase AC power is

 

 

 

 

missing. Check fuses etc.

 

 

 

2

Thermal Switch Fault. A thermal switch (fan cooled units only) detected an over

 

 

 

 

temperature condition. P51 (or P95) bit 5 enabled.

 

 

 

3 *

Thyristor Signal Fault. Thyristor control signal fault.

 

 

 

4 *

Thyristor Firing Fault. One or more thyristors not firing.

 

 

 

5 *

Thyristor Signal Fault. Thyristor control signal fault.

 

 

 

6 *

Thyristor Signal Fault. Thyristor control signal fault.

 

 

 

7 *

Thyristor Sensing Signal Fault.

 

 

 

8 *

Thyristor Sensing Signal Fault.

 

 

 

9 *

Thyristor Sensing Signal Fault.

 

 

 

10 * Thyristor Short Circuit. Thyristor shorted across the poles.

 

 

 

11

Under Current Fault. When •Top of Ramp" is reached, P28 (or P87) Low

 

 

 

 

Current Level and P29 (or P88) Low Current Time become active. If P51, Bit 4

 

 

 

 

is enabled, a fault will occur if the output current is less than P28 for longer

 

 

 

 

than the P29 time period.

 

 

 

12

Current Limit Fault. During start-up, P30 (or P89) Current Limit Level and P31

 

 

 

 

(or P90) Current Limit Time are active. If P51, Bit 1 is enabled, a fault will occur

 

 

 

 

if the output current exceeds P30 for longer than the P31 time period.

 

 

 

13

Overload Fault. During normal operation, P34 (or P93) Overload Level and P35

 

 

 

 

(or P94) Overload Delay are active. If P51, Bit 2 is enabled, a fault will occur if

 

 

 

 

the output current is equal to or greater than P34 for longer than the P35 time

 

 

 

 

period.

 

 

 

14

Shearpin Fault. When •Top of Ramp" is reached, P32 (or P91) Shearpin Level

 

 

 

 

and P33 (or P92) Shearpin Time become active. If P51, Bit 3 is enabled, a fault

 

 

 

 

will occur if the output current is greater than P32 for longer than the P33 time

 

 

 

 

period.

 

 

 

15

Thermistor Fault. Motor is overtemperature.

 

 

 

16

External Trip.

 

 

 

*

Contact Baldor if this fault occurs.

 

 

 

 

Parameters

P74

2nd Last Trip

P74 stores the trip code for the fault previous to P73. See P73 for definitions.

 

 

 

 

 

P75

3rd Last Trip

P75 stores the trip code for the fault previous to P74. See P73 for definitions.

 

 

 

 

 

P76

4th Last Trip

P76 stores the trip code for the fault previous to P75. See P73 for definitions.

 

 

 

 

 

P77

5th Last Trip (Oldest trip)

P77 stores the trip code for the fault previous to P76. See P73 for definitions.

 

 

 

 

 

P78

Protection Mode 2

Determines the fault protection method

 

 

(trips or 2nd param set)

0=

Input phase loss detection only.

 

 

 

64= Full protection with full volts after top of ramp.

 

 

 

128= Full protection during start then bypass (no protection)

 

 

 

192= Full protection + Optimization

 

 

 

 

 

P79

Start Pedestal 2

Sets the voltage level for the “Start of Voltage Ramp”. Must be

 

 

(for 2nd param set)

sufficient to allow motor to generate a breakaway torque.

 

 

 

 

 

P80

Start Time 2 (for 2nd param set)

Sets the time allowed for motor voltage to equal line voltage.

 

 

 

 

 

P81

Kick Pedestal 2 (for 2nd param set)

Sets the voltage level at the start of the kickstart operation.

 

 

 

 

 

P82

Kick Time 2 (for 2nd param set)

Sets the number of cycles that the P81 voltage is applied. Note that

 

 

 

for 60 Hz, 40 cycles = 667ms. For 50 Hz, 40 cycles = 800ms.

 

 

 

 

 

P83

Dwell 2 (for 2nd param set)

Sets the dwell time allowed after top of ramp is reached.

 

 

 

 

 

P84

Stop Pedestal 2 (for 2nd param set)

Sets the drop in motor voltage for the “Stop Voltage Ramp”

 

 

 

operation.

 

 

 

 

 

P85

Stop Time 2 (for 2nd param set)

Sets the ramp down time for motor stopping.

 

 

 

 

 

4-12 Parameter Index