Parameter Descriptions | Version 5MC | (4/2/01) |
|
|
| |
|
|
|
|
|
| |
Title | P# | Parameter |
|
| Description | |
Parameter | P0 | Dummy Parameter |
| Map unused bits, parameters etc. | ||
| P1 | Station Number |
| Unused |
| |
| P2 | Country |
| Determines the language used by the display. 44=English. | ||
| P3 | Software Type |
| Manufacturers product code for the | ||
| P4 | Software Version |
| Version of the software. | ||
Password | P5 | Password Value |
| Allows you to set and enter a password. | ||
Advanced | P6 | Firing Mode |
| 0= Normal motor (outside delta or star) | ||
|
|
|
| 1= Delta (inside delta, no optimization) | ||
|
|
|
| 2= Closed loop phase control | ||
|
|
|
| 3= Open loop phase control | ||
|
|
|
|
| ||
Basic | P7 | Protection Mode |
| Determines the fault protection method. | ||
|
|
|
| 0= | Input phase loss detection only. | |
|
|
|
| 64= | Full protection with full volts after top of ramp. | |
|
|
|
| 128= | Full protection during start then bypass (no protection) | |
|
|
|
| 192= | Full protection + Optimization | |
|
|
|
|
|
| |
Parameters | P8 | Status 1 |
|
| Definition (Preset Value, all = 0) | |
|
|
|
| Bit0= | Stopped (1=Start/stop signal inactive, SCR's Off, Main contactor open). | |
|
|
|
| Bit1= | Starting (1= Starter is in Start Ramp). | |
|
|
|
| Bit2= | Current Limit (1=Motor current has reached limit and is being held). | |
|
|
|
| Bit3= | Top of Ramp (Full volts) (1=start ramp and current limit is complete). | |
|
|
|
| Bit4= | Dwell (1=the time at the end of the start ramp when the motor is | |
|
|
|
|
| held at full volts before optimizing to stabilize the load). | |
|
|
|
| Bit5= | Full Conduction- (1= thyristors in continuous conduction). | |
|
|
|
| Bit6= | Energy Saving (1=Motor pf is monitored and volts are adjusted to optimum) | |
|
|
|
| Bit7= | Stopping (1=the stop ramp is active). | |
|
|
|
|
|
| |
| P9 | Status 2 |
|
| Definition (Preset Value, all = 0) | |
|
|
|
| Bit0= | Alarm (1=fault is detected and a trip has occurred) | |
|
|
|
| Bit1= | Overload Integrating (1=overcurrent is detected and is integrating) | |
|
|
|
| Bit2= | Stall (1=a stall condition is detected, motor speed decreasing). | |
|
|
|
| Bit3= | Forced Override (1= Optimizing not available even if selected because | |
|
|
|
|
| motor current>80%FLA). | |
|
|
|
| Bit4= | Noise (1=Noise on AC input power mains is detected). | |
|
|
|
| Bit5= | Inhibit Start (1=Start is inhibited for a period to maintain duty cycle). | |
|
|
|
| Bit6= | DC I/P level reached (1= DC > P48). | |
|
|
|
| Bit7= | ||
|
|
|
|
|
| |
| P10 | Status 3 |
|
| Definition (Preset Value, all = 0) | |
|
|
|
| Bit0= | K1 (1= K1 | Active). |
|
|
|
| Bit1= | K2 (1= K2 | Active). |
|
|
|
| Bit2= | K3 (1= K3 | Active). |
|
|
|
| Bit3= | K4 (1= K4 | Active). |
|
|
|
| Bit4= | Starter I/P 1 (1= Control Input1 is high). | |
|
|
|
| Bit5= | Starter I/P 2 (1= Control Input2 is high). | |
|
|
|
| Bit6= | Starter I/P 3 (1= Control Input3 is high). | |
|
|
|
| Bit7= | Red LED status (unused) | |
|
|
|
|
| ||
Basic | P11 | Start Pedestal |
| Sets the voltage level for the •Start of Voltage Ramp". Must be sufficient to allow | ||
|
|
|
| motor to generate a breakaway torque. | ||
|
|
|
|
| ||
| P12 | Start Time |
| Sets the time allowed for motor voltage to equal line voltage. | ||
Advanced | P13 | Kick Pedestal |
| Sets the voltage level at the start of the kickstart operation. | ||
| P14 | Kick Time |
| Sets the number of cycles that the P13 voltage is applied. Note that for | ||
|
|
|
| 60 Hz, 40 cycles = 667ms. For 50 Hz, 40 cycles = 800ms. | ||
|
|
|
|
| ||
| P15 | Dwell Time |
| Sets the dwell time allowed after top of ramp is reached. | ||
Basic | P16 | Stop Pedestal |
| Sets the drop in motor voltage for the •Stop Voltage Ramp" operation. | ||
| P17 | Stop Time |
| Sets the ramp down time for motor stopping. | ||
Auto Features | P18 | Auto Config |
| Auto configuration flags to use with the first parameter set. | ||
|
|
|
|
| Definition (Preset Value) | |
|
|
|
| Bit0= | Unused |
|
|
|
|
| Bit1= | Auto 3MC (1, Auto remove low volt. ramp for high start pedestal). | |
|
|
|
| Bit2= | Auto Bypass (1, Enable Automatic Bypass Contactor detection). | |
|
|
|
| Bit3= | Auto Jog (0, Disable auto jog detect. If 1, a stop request within .5 sec | |
|
|
|
|
| of a start request is forced to 0 stop time). | |
|
|
|
| Bit4= | Auto Endstop (0, Do not detect stalled motor at softstop). | |
|
|
|
| Bit5= | Auto Stop (0, Do not detect variations in pf during stop smooth stall). | |
|
|
|
| Bit6= | Auto Endstart (0, Do not detect full speed at start and adjust start ramp). | |
|
|
|
| Bit7= | Auto Pedestal (0, Do not detect rotation at start and adjust pedestal). | |
|
|
|
|
| ||
Advanced | P19 | Optimise Rate |
| Sets the optimizing response rate. This parameter helps to stabilize small slip speed | ||
|
|
|
| motors with low inertia loads. (4=fastest optimizing rate). | ||
|
|
|
|
|
|
|
| MN850 |