NEMA 12/4 Installation When a NEMA12, NEMA4, NEMA4x OR IP65 enclosure is used, a separate Top of Ramp Bypass (or shunt) contactor must be connected in parallel with the soft–start control. This will allow a solid connection of the motor to the AC power lines and eliminate the heating effect caused by the SCR’s. At the completion of the start ramp (when full start voltage is obtained) a Bypass contactor is closed. This contactor is controlled by the “Top of Ramp” relay K2. This ensures that bypass will only occur when motor voltage equals the AC line voltage.

Figure 2-6 Top of Ramp (Bypass) Connection

115/230VAC

 

 

To AC Input

 

 

 

 

 

 

 

 

To protect the control, be sure to add MOV protection.

 

 

 

 

 

 

 

Fuse

Neutral

 

 

 

 

 

Refer to Appendix D for additional information.

 

 

 

 

 

 

 

 

 

X1

 

L1

L2

L3

 

 

 

 

X2

 

 

 

 

 

 

 

 

S1

 

 

Baldor

 

 

Note:

BC

S0

 

 

* BC

Bypass

 

 

 

 

Digital

 

Contactor

Add appropriately rated

14

 

 

Soft–Start

 

 

protective device for AC

11

K1

 

 

 

12

 

 

 

 

 

relay (snubber) or DC

 

 

 

 

 

 

 

 

 

 

 

 

 

relay (diode).

24

 

K2 is factory preset

 

 

 

 

 

21

K2

 

 

 

 

 

22

as the •Top of Ramp" function.

 

 

 

 

 

* External hardware not provided with control.

 

 

T1

T2

T3

 

 

 

 

 

 

 

 

 

See Recommended Tightening Torques in Table 2-4.

 

 

 

 

 

 

 

 

 

 

 

To Motor

 

 

 

2-10 Installation

MN850

Page 15
Image 15
Baldor Baldor, MN850 manual Top of Ramp Bypass Connection, 115/230VAC