Input Ratings

Input Voltage Range

MD7–XXX= 208/230/460 VAC +10% to –15%

 

MD8–XXX= 230/460/575 VAC +10% to –15%

Phase

Three Phase

Input Frequency

60/50 HZ ± 5%

Overload Rating

Continuous 115% of FLA; 350% for 30 seconds.

Duty Cycle

Continuous

Peak Inverse Voltage

MD7–XXX= 1400VAC maximum

 

MD8–XXX= 1600VAC maximum

S0, S1

12VDC or 24VDC

X1, X2

115VAC (98 – 126VAC) or 230VAC (196 – 253VAC)

Storage Conditions

 

Ambient Temperature:

–4 to 140° F (-20 to 60 ° C)

Humidity:

0 - 95% RH Non-Condensing

Operating Conditions

 

Enclosure:

NEMA 1 – Wall mounted (Industrial indoor, general purpose)

 

For other enclosures, contact Baldor.

 

The SCR’s generate about 3.3 watts of heat per running amp (motor

 

FLA). If the control is mounted in an enclosure, the installer must

 

provide fans or blower with sufficient ventilation. Fan or blower

 

should be rated for at least 0.8 CFM per ampere of motor FLA rating.

 

Baldor provided enclosures are designed to dissipate the heat from

 

the SCR’s.

Humidity:

0 - 85% RH Non-Condensing (not to exceed 50% at 40° C ambient).

Control Heat Loss

3.3 Watt per running ampere of input current

Ambient Operating Temperature:

32-113°F (0 to +40 ° C) enclosed

 

32-122°F (0 to +40 ° C) open panel

Altitude:

Sea level to 3300 Feet (1000 Meters)

 

Derate 1% per 330 Feet (100 Meters) above 3300 Feet

Derating

Derate Amp rating 1% per 330 Feet (100 Meters) above 3300 Feet

 

Derate Amp rating 2% per ° C over 40 ° C to 60 ° C Max

Output Relays – K1 and K2 contacts

Category AC1, 230VAC, 3A.

6-2 Specifications and Product Data