AC Main Circuit
Power Disconnect A power disconnect should be installed between the input power service and the control for a fail safe method to disconnect power.
Protective Devices Recommended fuse sizes are based on the following: 175% of maximum continuous current for time delay.
300% of maximum continuous current for Fast or Very Fast action.
Note: These general size recommendations do not consider harmonic currents or ambient temperatures greater than 40° C.
Be sure a suitable input power protection device is installed. Use the recommended circuit breaker or fuses listed in Table
Circuit Breaker: | 3 phase, thermal magnetic. |
| Equal to GE type THQ or TEB for 230VAC or |
| Equal to GE type TED for 460VAC and 575VAC. |
Fast Action Fuses: | 230VAC, Buss KTN |
| 460VAC, Buss KTS to 600A (KTU for 601 to 1200A) |
Very Fast Action: | 230VAC, Buss JJN |
| 460VAC, Buss JJS |
Time Delay Fuses: | 230VAC, Buss FRN |
| 460VAC, Buss FRS to 600A (KLU for 601 to 1200A) |