Baldor MN850 manual In-Delta Soft-Start Connections, Baldor Digital

Models: MN850 Baldor

1 70
Download 70 pages 3.46 Kb
Page 12
Image 12

In–Delta Connections For Delta connected motors, the Soft–Start can be connected inside the delta windings. This connection method is shown in Figure 2-2.

 

 

 

Figure 2-2

In–Delta Soft–Start Connections

 

 

 

 

L1

L2

L3

 

 

 

 

L1

L2

L3

 

 

 

 

Earth

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1

* Circuit

 

 

 

 

 

Alternate *

 

 

 

 

Note 2

 

Fuse

 

 

Note 1

 

Breaker

 

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Optional components not provided with control.

Note 3, 9

 

 

 

 

 

 

 

 

 

 

 

L1

L2

L3

 

 

 

 

 

 

 

 

 

 

 

 

X1

115/230VAC

 

 

 

 

 

 

 

 

 

X2

In–Delta connections for correct motor rotation

 

 

Baldor

 

Note 6, 7

 

 

Digital

 

 

 

Soft–Start

Motor

 

 

 

 

Soft–Start

 

 

 

 

 

 

 

 

 

 

Terminal

Terminal

 

 

 

T1

T2

T3

 

 

 

T1

T3

 

 

 

 

 

 

T2

T1

 

 

 

 

 

 

 

 

 

T3

T2

 

 

 

 

T1

 

 

 

L1

T5

 

 

 

 

T3

T2

 

 

 

L2

T6

 

 

 

* AC Motor

 

G

 

 

 

L3

T4

 

 

 

 

T5

T4

 

 

 

 

 

 

 

 

 

T6

 

 

 

 

 

 

 

 

Note 8

 

 

 

 

 

 

 

 

 

 

See Recommended Tightening Torques in Table 2-4.

Notes:

1.See “Protective Devices” described previously in this section.

2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.

3.Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.

4.Derating factor for soft–start is 57%.

5.Parameter P6– Firing Mode must be set to 1.

6.X1 and X2 control terminal power must be present or the logic circuits will not work. Either 115VAC or 230VAC can be used. Be sure the 115/230VAC switch (Control Voltage Selector Switch) is set to the proper voltage before you apply power.

7.The X1 and X2 control voltage input has different VA ratings depending on enclosure size, see Table 2-3.

8.For reversing operation, L1 and L2 should be switched. Reversing any two of the three input phases will reverse the motor rotation.

9.To protect the control, be sure to add MOV protection. Refer to Appendix D for additional information.

Fan Connections – Size 3 and 4 only Size 1 and 2 controls do not have fan connections. For Size 3 controls make the fan connections as shown in Figure 2-3.The Fan and Control voltages must be the same (both must be 115VAC or both must be 230VAC). 150VA (minimum) required.

Figure 2-3 Fan Connections

115V Connections

230V Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X1

X2

(150VA minimum)

X1

X2

MN850

Installation 2-7

Page 12
Image 12
Baldor MN850 manual In-Delta Soft-Start Connections, Baldor Digital