DS-RPC OWNER’S MANUAL INSTALLATION

__________________________________________________________________________________________

CAUTION: For PERMANENTLY CONNECTED EQUIPMENT, a readily accessible disconnect device shall be incorporated in the fixed wiring. For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and easily accessible.

Applying power illuminates a green LED on the front panel of the DS- RPC. When the power switch is off, devices connected to the unit are not receiving power.

POWER ON/OFF STATE

Each receptacle is individually controlled by an internal relay. Upon initialization of power, the status of each receptacle will return to the state it was in prior to losing power. For example, if Outlet 1 and Outlet 2 are “ON” and power is removed from the DS-RPC, the status of Outlet 1 and Outlet 2 will return to “ON” when power is restored to the DS-RPC.

POWER UP SEQUENCE

In order to minimize power surges, the DS-RPC sequences power to each outlet in the “ON” state in 0.3-second intervals. When power is applied to the DS-RPC, the initialization sequence requires a delay of 10 seconds before power is available at the service receptacles. Following the 10- second delay, the DS-RPC sequences power to each outlet that is turned “ON.” If you choose the option requesting the DS-RPC to reboot all connected equipment, the DS-RPC sequences power to each outlet turned “ON” in 0.1-second intervals.

CIRCUIT BREAKER

In the case of power overload, the circuit breaker automatically trips. Determine the cause of the tripped circuit breaker, correct the problem then reset the circuit breaker by depressing the circuit breaker switch.