Bosch Appliances D6600, D6100 manual DSC 4-3Message Type d, Computer Communication Protocols

Models: D6100 D6600

1 168
Download 168 pages 55.61 Kb
Page 36
Image 36
3.2.11 DSC 4-3 (Message Type d)

Conettix D6600/D6100 Computer Interface Manual

3.0

Computer Communication Protocols

 

 

 

3.2.11 DSC 4-3 (Message Type d)

DSC4-3 Example

SIA Mode Description

<LF><CRC><d><sequence#><receiver#><line#>[#aaaaXYY]<CR>

Table 53: DSC 4-3 (Message Type d) Byte Description

 

 

 

 

 

 

Title

 

Description

 

LF

 

Standard line feed character.

 

CRC

 

Cyclical redundancy check number.

 

Message Type

 

d

 

sequence#

 

The message sequence number. The valid sequence number range is 0001 to 9999.

 

 

 

 

 

 

receiver#

 

 

The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600/D6100.

 

line#

 

The line number of the line in the receiver gateway that sent the message. Valid digits are 00

 

(Line/Group #)

 

to 99. The receiver uses Line 0 (zero) for internal messages.

 

 

 

 

 

account#

 

The communicator's account number has four digits.

 

X

 

Event code number.

 

YY

 

 

Zone number.

Figure 15: Message sent to printer

mm/ddshh:mmsLxxsDSGsACCTsaaaasEVENT=XY

Y+++sACCsaaaaseeeeeeeesiisnnn

For lines that are grouped, Gxx appears instead of Lxx.

Table 55: Event Code Table

 

 

 

Code Number

Message

Event

 

 

Characters

 

 

 

1

Alarm

A

2

 

A

3

 

A

4

Close

C

5

Open

O

6

Alarm

A

 

 

 

7

 

A

 

 

 

8

 

A

9

Restore

R

0

Trouble

T

 

 

 

B

CloseGrp

C

C

OpenGrp

O

D

Bypass

B

E

UnBypass

H

F

Cancel

O

Table 54: DSC 4-3 (Message Type d) Printer

 

Output

 

 

 

 

 

 

Characters

 

Description

DSG

 

DSC/Sur-Gard 4-3 format.

Lxx:

 

Line number.

Gxx

 

Grouped line numbers.

Table 56: Printer Output Codes

Characters

Description

ii

ZN=Zone number - ID=User ID

nnn

Zone/User number.

eeeeeeeeUp to eight-character event type, right justified – ALARM, RESTORE, TROUBLE, OPEN, OPENGRP, CLOSE, CLOSEGRP, BYPASS, UN BYPASS, CANCEL.

36

Bosch Security Systems, Inc. 1/07 4998122703-01

Page 36
Image 36
Bosch Appliances D6600, D6100 manual DSC 4-3Message Type d, Computer Communication Protocols