Bosch Appliances D6600, D6100 Silent Knight FSK2 Message Type m, Computer Communication Protocols

Models: D6100 D6600

1 168
Download 168 pages 55.61 Kb
Page 46
Image 46
3.2.24 Silent Knight FSK2 (Message Type m)

Conettix D6600/D6100 Computer Interface Manual

3.0

Computer Communication Protocols

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 77: Silent Knight FSK1 Optional Outputs (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Report Code

Description

To Automation

 

 

Note

 

 

 

 

 

 

 

 

 

 

90

Opening

OP00

 

90

 

 

 

91 to 99

Opening 01 to 09

OP0x

 

91 to 99

 

 

3.2.24 Silent Knight FSK2 (Message Type m)

Silent Knight FSK2 Example

SIA Mode Description

<LF><CRC><m><sequence#><receiver#><line#>[#aaaaaa

EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]<CR>

Table 78: Silent Knight FSK2 (Message Type m) Byte Description

 

 

Title

Description

LF

Standard line feed character.

CRC

Cyclical redundancy check number.

 

 

Message Type

m

sequence#

The message sequence number. The valid sequence number range is 0001 to 9999.

receiver#

The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.

line#

The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to

(Line/Group #)

99. The receiver uses Line 0 (zero) for internal messages.

account #

The communicator's account number has up to six digits.

EEZZ”EEZZ”EEZZ”EEZZ”

Up to eight reports. One report has four digits: one-digit event code, one-digit condition code,

EEZZ”EEZZ”EEZZ”EEZZ

and two-digit zone code. The quote (“) is the separation character.

 

 

46

Bosch Security Systems, Inc. 1/07 4998122703-01

Page 46
Image 46
Bosch Appliances D6600, D6100 Silent Knight FSK2 Message Type m, Computer Communication Protocols, Eezz”Eezz”Eezz”Eezz”