Bosch Appliances D6600, D6100 manual Seriee DTMF Message Type l, Seriee FSK Message Type k

Models: D6100 D6600

1 168
Download 168 pages 55.61 Kb
Page 42
Image 42
3.2.19 Seriee DTMF (Message Type l)

Conettix D6600/D6100 Computer Interface Manual

3.0

Computer Communication Protocols

 

 

 

3.2.19 Seriee DTMF (Message Type l)

Seriee DTMF Example

SIA Mode Description

<LF><CRC><l><sequence#><receiver#><line#>[#aaaa*data]<CR>

Table 70: Seriee DTMF (Message Type l) Byte Description

 

 

 

 

 

 

Title

 

Description

 

LF

 

Standard line feed character.

 

CRC

 

Cyclical redundancy check number.

 

Message Type

 

l (lowercase L).

 

sequence#

 

The message sequence number. The valid sequence number range is 0001 to 9999.

 

 

 

 

 

 

receiver#

 

 

The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600/D6100.

 

line#

 

The line number of the line in the receiver gateway that sent the message. Valid digits are 00

 

(Line/Group #)

 

to 99. The receiver uses Line 0 (zero) for internal messages.

 

 

 

 

 

account #

 

The communicator's account number has four digits.

*

 

 

Data separator.

 

Data

 

 

DTMF Seriee Data.

3.2.20 Seriee FSK (Message Type k)

Seriee FSK Example

SIA Mode Description

<LF><CRC><k><sequence#><receiver#><line#>[#aaaaaEZZ]<CR>

Table 71: Seriee FSK (Message Type k) Byte Description

 

 

 

 

 

 

Title

 

Description

 

LF

 

 

Standard line feed character.

 

CRC

 

Cyclical redundancy check number.

 

Message Type

 

k

 

sequence#

 

The message sequence number. The valid sequence number range is 0001 to 9999.

 

 

 

 

 

receiver#

 

The receiver gateway that sent the message. Valid digits are 01 to 99 for D6600/D6100.

 

line#

 

The line number of the line in the receiver gateway that sent the message. Valid digits are 00 to

 

(Line/Group #)

 

99. The receiver uses Line 0 (zero) for internal messages.

 

 

 

 

 

Account #

 

The communicator's account number has up to six digits.

 

E

 

Event code.

 

ZZ

 

Zone number.

 

 

 

 

 

42

Bosch Security Systems, Inc. 1/07 4998122703-01

Page 42
Image 42
Bosch Appliances D6600, D6100 manual Seriee DTMF Message Type l, Seriee FSK Message Type k, Computer Communication Protocols