Bosch Appliances D6100 Message sent to printer, MM/DDsHH:MMsLxxSIA +++TEXT +++TEXT, Isaaaaaaaaaaa

Models: D6100 D6600

1 168
Download 168 pages 55.61 Kb
Page 35
Image 35
Figure 13: Message sent to printer

Conettix D6600/D6100 Computer Interface Manual

3.0

Computer Communication Protocols

 

 

 

Undefined Messages

When a common format message contains unprintable hex characters (unprintable characters are out of ASCII range 0x32-0x7E) or without an account block:

SIA Example

SIA Mode Description

<LF><CRC><TAB><sequence#><receiver#><line#>[data]<CR>

Table 51: Common Formats (Message Type <TAB>) Byte Description

 

 

 

 

 

Title

Description

 

 

 

 

 

LF

 

Standard line feed character.

 

CRC

Cyclical Redundancy Check number.

 

 

 

 

Message Type

09 hex.

 

sequence#

The message sequence number. The valid sequence number range is 0001 to 9999.

 

receiver#

 

The receiver gateway that sent the message. Valid digits are 01 to 99 for the

 

 

 

D6600/D6100.

 

line#

The line number of the line in the receiver gateway that sent the message. Valid digits are 00

 

(Line/Group #)

to 99. The D6600 uses Line 0 (zero) for receiver gateway messages.

 

Data

The receiver message contains hex characters either with or without account portion.

Figure 13: Message sent to printer

MM/DDsHH:MMsLxx[SIA]

+++TEXT 1

+++TEXT 2

3.2.10 DNIS/ANI (Message Type N)

SIA Example

SIA Mode Description

<LF><CRC><N><sequence#><receiver#><line#>[#0000Dddddddddddd&aaaaaaaaaa]

<CR>

Table 52: DNIS/ANI (Message Type N) Byte Description

 

 

 

 

 

 

Title

 

Description

 

 

 

 

 

 

LF

 

Standard line feed character.

 

CRC

 

Cyclical redundancy check number.

 

 

 

 

 

 

Message Type

 

 

N

 

sequence#

 

The message sequence number. The valid sequence number range is 0001 to 9999.

 

receiver#

 

The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600/D6100.

 

line#

 

The line number of the line in the receiver gateway that sent the message. Valid digits are 00

 

(Line/Group #)

 

to 99. The receiver uses Line 0 (zero) for internal messages.

 

account#

 

Fixed at 0000.

 

D

 

DNIS identified.

 

 

 

 

 

DNIS number (d)

 

DNIS number, up to 11 digits.

 

ANI identifier (&)

 

ANI identifier.

 

ANI number (a)

 

ANI number, up to 11 digit.s

Figure 14: Message sent to printer

MM/DDsHH:MMsLxxsDNISsddddddddddd+++sAN

Isaaaaaaaaaaa

Bosch Security Systems, Inc. 1/07 4998122703-01

35

Page 35
Image 35
Bosch Appliances D6100 Message sent to printer, MM/DDsHH:MMsLxxSIA +++TEXT +++TEXT, DNIS/ANI Message Type N, Isaaaaaaaaaaa