D9412G/D7412G Program Entry Guide 6.0 RADXAUX1
EN 126
Parity/Stop
Default: | No/1 |
|
|
Selection: | No/1, No/2, Odd/1, Even/1 |
No/1 | No parity, 1 stop bit. |
|
|
No/2 | No parity, 2 stop bits. |
|
|
Odd/1 | Odd parity, 1 stop bit. |
|
|
Even/1 | Even parity, 1 stop bit. |
|
|
This prompt addresses two items: Parity and the number of stop bits for the
This item must be set to No/1 when using the External Modem feature.
RTS Control
Default: | On | |
Selection: | On, AutoX, Off, AutoR | |
On | Sets RTS to on (hardware control). | |
|
| |
Auto X | Automatically enables Xon/Xoff | |
| (software control). | |
|
| |
Off | Sets RTS off (hardware control). | |
|
| |
Auto R | Sets this to Auto RTS. | |
|
|
Determines how the Request To Send Control parameters are defined for the
This item must be set to On when using the External Modem feature.
DTR Control
Default: | On |
Selection: | On, AutoD, Off |
On | Sets DTR to on (hardware control). |
|
|
AutoD | Sets this to Auto DTR. |
|
|
Off | Sets DTR off (hardware control). |
|
|
Determines how the Data Terminal Ready Control parameters are defined for the
This item must be set to On when using the External Modem feature.
9133 Supervision
Default: | No |
|
|
Selection: | Yes or No |
Yes | Supervise the |
| Interface Module. |
|
|
No | Do not supervise the |
| Network Interface Module. |
|
|
This item determines whether the
Trouble SDI 88 Reports are always reported using Area 1’s account number.
Base Port Number
Default: 7700
Selection: 0 to 65535
The base port number is the port number of the CoBox , such as 7700. This is used in the future revision and is not needed at this time.
6.6.1Route Group Attempts
This section determines how many times a route group tries the primary destination before attempting the backup destination should the primary destination fail. This entry applies to both Phone numbers and IP addresses.
Bosch Security Systems 1/04 47775E