Bosch Appliances D9412G, D7412G manual Base Port Number, Route Group Attempts

Models: D7412G D9412G

1 142
Download 142 pages 15.12 Kb
Page 126
Image 126

D9412G/D7412G Program Entry Guide 6.0 RADXAUX1

EN 126

Parity/Stop

Default:

No/1

 

 

Selection:

No/1, No/2, Odd/1, Even/1

No/1

No parity, 1 stop bit.

 

 

No/2

No parity, 2 stop bits.

 

 

Odd/1

Odd parity, 1 stop bit.

 

 

Even/1

Even parity, 1 stop bit.

 

 

This prompt addresses two items: Parity and the number of stop bits for the D9133TTL-E. Pressing the [SPACE] bar on the D5200 toggles through the available options.

This item must be set to No/1 when using the External Modem feature.

RTS Control

Default:

On

Selection:

On, AutoX, Off, AutoR

On

Sets RTS to on (hardware control).

 

 

Auto X

Automatically enables Xon/Xoff

 

(software control).

 

 

Off

Sets RTS off (hardware control).

 

 

Auto R

Sets this to Auto RTS.

 

 

Determines how the Request To Send Control parameters are defined for the D9133TTL-E. Pressing the [SPACE] bar on the D5200 toggles through the available options.

This item must be set to On when using the External Modem feature.

DTR Control

Default:

On

Selection:

On, AutoD, Off

On

Sets DTR to on (hardware control).

 

 

AutoD

Sets this to Auto DTR.

 

 

Off

Sets DTR off (hardware control).

 

 

Determines how the Data Terminal Ready Control parameters are defined for the D9133TTL-E. Pressing the [SPACE] bar on the D5200 toggles through the available options.

This item must be set to On when using the External Modem feature.

9133 Supervision

Default:

No

 

 

Selection:

Yes or No

Yes

Supervise the D9133TTL-E Network

 

Interface Module.

 

 

No

Do not supervise the D9133TTL-E

 

Network Interface Module.

 

 

This item determines whether the D9133TTL-E is supervised or not. If the D9133TTL-E is supervised, disconnecting it from the control panel creates a Trouble SDI 88 Event and the command centerannunciates a trouble tone and displays SERVC SDI 88.

Trouble SDI 88 Reports are always reported using Area 1’s account number.

Base Port Number

Default: 7700

Selection: 0 to 65535

The base port number is the port number of the CoBox , such as 7700. This is used in the future revision and is not needed at this time.

6.6.1Route Group Attempts

This section determines how many times a route group tries the primary destination before attempting the backup destination should the primary destination fail. This entry applies to both Phone numbers and IP addresses.

Bosch Security Systems 1/04 47775E

Page 126
Image 126
Bosch Appliances D9412G, D7412G manual Base Port Number, Route Group Attempts