D9412G/D7412G Program Entry Guide 2.0 9000MAIN

EN 70

A# Area Armed

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C

Activates when the specified area becomes master armed (exit delay must expire before the relay activates). The relay remains activated until the area is disarmed. It does not deactivate during the entry delay time.

If multiple areas use the same relay, the relay activates when all areas are armed. It deactivates when the first area disarms.

Programming a 64 in Area 8’s Silent Alarm relay causes the Area Armed relay to energize at the beginning of the exit delay time.

Keyswitch area armed status with LEDs. Use a D8129 Module and connect an LED to display the armed state.

Alternate communication trigger: This output relay can be used to trigger the input zone of a device being used as a slave to report control panel arming status.

A# Area Fault

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C

The relay activates whenever a controlled (P## Type 1, 2, 3 only) Perimeter or Interior point is faulted. The relay remains activated until all Perimeter and Interior points in the area are normal.

Keyswitch area armed status with LEDs. Use a D8129 Module and connect an LED to light when this relay is activated indicating that the area is not ready to arm.

A# Duress Relay

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C

The relay activates when a Duress alarm is generated from a command center assigned to the specified area.

 

Burg Time needs a bell period

0101

programmed and A# Duress Enable must

 

be Yes. This relay activates steadily

 

regardless of bell pattern and remains

 

active until the bell time expires.

A# Perim Fault

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C

The relay activates when a Controlled Perimeter point (P## Type 1) assigned to the specified area is faulted. This relay activates regardless of the areas armed state. This relay provides a steady output until all Perimeter points in the area return to normal.

This relay does not activate on interior faults. To detect all area point faults, program all points as Perimeter points in the area where this relay is assigned.

A# Silent Alarm

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C

This relay activates when a point assigned to the specified area and programmed for P## Silent Bell goes into alarm.

 

Programming Tip #1: Burg Time needs a

0101

bell period programmed. This relay

 

activates according to the bell pattern and

 

remains active until the bell time expires or

 

a valid passcode is entered.

 

Programming Tip #2: Programming 64 in

0101

Area 8’s Silent Alarm Relay causes the

 

Area Armed or Perimeter Armed Relay

 

(see Programming Tip #5) to energize at

 

the beginning of the exit delay time.

 

Programming Tip #3: Programming a

0101

non-zero value in Area 5’s Silent Alarm

 

Relay enables Ground Fault Detect on the

 

D9412G or D7412G Control Panels. See

 

the D9412G/D7412G Operation and

 

Installation Guide regarding Ground Fault

 

Detect.