D9412G/D7412G Program Entry Guide 5.0 RADXSKED
EN 111
24
No Entry Events Off: The control panel can log No Entry Events when an invalid token is detected for a specific door. No Entry Events include No
S## Door 1 [through 8]
Default: No
Selection: Yes or No
This parameter disables the reporting of No Entry Events for Door #.
Yes
No
Enable the reporting of No Entry Events for Door #.
Do not enable the reporting of No Entry Events for Door #.
Sked Functions 28 and 29 are available only in firmware versions 6.30 and higher. RPS version 3.5 and RADXSKED handler version 1.02 and higher must be used to program these new skeds.
28
Expanded
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated and the
To meet UL 864 daily Test Report requirements (when using two phone lines) you must still use Sked Function Code 9, Test Report and program it to occur on a daily basis as per AHJ requirements.
29
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated and the
To meet UL 864 daily Test Report requirements (when using two phone lines), you must still use Sked Function Code 9, Test Report and program it to occur on a daily basis as per AHJ requirements.