D9412G/D7412G Program Entry Guide 4.0 RADXPNTS

EN 82

P## Pt Response

Default:

See Program Record Sheet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection:

0 to F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controlled (Non-24-Hour Points)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Point Response

0

1

2

3

4

 

5

6

7

8

 

9

A

B

C

D

E

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Armed

Open

I

I

I

I

D

 

D

I

I

D

 

I

I

I

I

I

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Armed

Short

I

I

I

I

I

 

I

D

D

D

 

I

I

I

I

I

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disarmed

Open

 

T

 

T

 

 

 

 

T

 

 

I

I

T

I

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disarmed

Short

 

 

T

T

 

 

T

 

 

 

 

I

T

I

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-Hour Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Point Response

0

1

2

3

4

 

5

6

7

8

 

9

A

B

C

D

E

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

I

T

I

T

 

 

 

I

T

S

 

T

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Short

 

I

I

T

T

I

 

T

 

 

T

 

S

 

S

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Key:

I = Instant alarm

 

D = Delayed alarm

 

T = Trouble

 

S = Supervisory

 

Blank = Audible/visual response

Example of Controlled point:

Point Type = 1

Point Response = 8

Perimeter point with delayed alarm response when armed (opened or shorted) and no response when disarmed.

Example of 24-hour point:

Point Type = 0

Point Response = 8

24-hour point with supervisory response when open and a trouble response when shorted.

When programming the point response for Inovonics Wireless Transmitters, regardless of how the transmitter is programmed, the D8125INV Wireless Interface always sends the off-normal state to the control panel as a short and a tamper condition as an open. As a result, typical point responses for the Inovonics transmitters would include 0, 1, 6, 7, and E for Controlled points, and 0 and 1 for 24-hour Burg points. When programming a transmitter as a Fire point, a Point Response of 1 is recommended.

Note:

Wireless transmitters are NOT UL Listed with the D9412G/D7412G in fire or burglary applications. At present, Inovonics Wireless Transmitters, when used with the D8125INV Wireless Interface on a 9000 Series Control Panel, are not UL Listed for use with fire or burglary applications.

With Supervisory Pt Response (S = Supervisory), the BFSK format does not transmit fire supervisory or Non-fire Supervisory Events. Modem format must be used with Supervisory Point Responses.

Bosch Security Systems 1/04 47775E