D9412G/D7412G Program Entry Guide 7.0 RADXAXS

EN 131

7.0 RADXAXS

7.1Door Profile

This programming category is used to:

Assign an area, that also activates the D9210B

Assign a point to the door

Program the door state to change when the arm state changes

Allow for the Strike relay to activate upon a fire alarm

Door #

Default: 20 seconds

Selection: 1 seconds to 8 seconds

Enter the number of the door you are about to program.

The D9412G supports up to eight doors.

The D7412G supports two doors.

D# Entry Area #

Default: Blank

Selection: Blank, 1 to 8

1 to 8

The area assigned to the door

 

controller to which the reader allows

 

access.

 

 

Blank

Door controller does not function.

 

 

Assign an area to the door controller. This entry allows the D9210B to be polled, activating communication to the control panel. This also is the area a user exits when initiating a REX.

All SDI devices, regardless of area assigned, report to Area 1, Account 1 by default upon SDI failure. If a D9210B becomes disconnected, an SDI Fail ## and a Missing Point ### Event is created.

 

9210 NOT READY appears at this

0101

command center when you press the

 

[ENTER] key if the D9210B is not

 

programmed with a D# Entry Area.

D#CC#Scope

Default: Blank

Selection: Blank, 1 to 8

1 to 8

Determines disarming rights. The

 

user’s access level in conjunction with

 

the CC # Scope determines which

 

areas are disarmed.

Blank

Only the area assigned to the D#

 

Entry Area disarms this door.

 

 

Enter the command center number (CC#) which determines the scope of the user ID’s disarming rights. Areas disarm on the basis of this command center’s scope and the authority level of the user.

D# Door Point

Default: Blank

Selection: Blank, 1 to 127, 129 to 247

1 to 127,

The point number assigned to this

129 to 247

door. Points 128 and 248 are reserved

 

by the control panel for internal use.

 

 

Blank

There is no point number assigned to

 

this door.

 

 

Enter the point number assigned to this door. This point cannot be used for any other point assignments.

Door points must be programmed as Perimeter points. If a 24-hour point type is required for the Door point, you may use a Perimeter point type with a point response of 9 to C. Also, the debounce count must be set to 4 in Point Assignments.

 

When assigning Points 1 to 8 (control

0101

panel zones), the end-of-line (EOL)

 

resistors must be removed from the control

 

panel. In addition to this, do not enable any

 

POPIT points (or OctoPOPIT points)

 

sharing the same point number as the

 

Door point. Failure to do so results in extra

 

point trouble conditions upon reboot.