D9412G/D7412G Program Entry Guide 1.0 Introduction

1.7Programming the Control Panel

with the D5200 Programmer

Latch the jumper in the upper right hand corner of the control panel labeled as RESET on the PCB and Reset Pin on the faceplate.

Connect the molex end of the cord to the connector labeled PROG on the PCB and PROG CONN on the faceplate.

Always initiate a control panel copy at the NEWRECORD or FILENAME display when pressing the [RECV] (copy) key of the D5200.

Always initiate a control panel load at the FILENAME prompt or set as factory default at the NEWRECORD prompt when pressing the [SEND] (load) key.

Disconnect the D5200 before releasing the reset pin.

Do not leave the D5200 connected to the PROG connector without latching the RESET pin. Doing so causes SDI ## TROUBLE and CALL FOR SERVICE to display on the command centers. Door controllers also activate depending upon the SDI failure DIP switch setting.

Table 5: Programming Error Displays

EN 9

Display

INCOMPATIBLE PANEL

CHECK CORD/RESET PIN

Description

You are connected to the wrong control panel or using the wrong handler. Check the faceplate for the model number and the handler title.

Check the cord and reset pin

 

There is a 5 second to 25 second pause

0101

after the reset pin is unlatched during

 

which the control panel scans all the

 

points and properly displays, logs, and

 

reports them.