11.1Digit 1, Point Type

2000 Series Program Entry Guide 11.0

Point Codes

 

 

EN 37

11.1Digit 1, Point Type

For Digit 1 selections 3, 4, 5, 6, 7, 8, 9, B, C: If an alarm occurs on these points within 2 minutes of a closing (exit time expired, Excursion/Exit included), the system sends a RECENT CLOSING message with the Alarm Report.

For Digit 1 selections 6, 7, 8, 9, B, C: If these points are faulted at the end of exit delay, the system waits a period equal to entry delay before sending an Alarm Report. If the system is not turned off, it sends an EXIT ERROR message with the Alarm Report.

Set Digit 1 to 0 (zero) for points used for RF keypads and arming devices: If you want to use an RF keypad or other arming device, you must assign each device to a point number in order to learn the device into the system. Set Digit 1 to 0 for RF keypad and arming device points.

Table 5: Digit 1 Selections

Display

Selection

 

Description

0

Disabled

Point does not respond to opens or shorts. Set Digit 1 to 0 if you are using

 

 

this point number for an RF Keypad or arming device.

1

Fire

 

Short on sensor loop starts fire alarm response.

 

 

Open on sensor loop causes trouble response.

 

 

Fire points are not bypassable. Single Ring programming option does not

 

 

apply to Fire points.

 

 

Missing Fire points generate a trouble response when the system is on or

 

 

off.

 

 

2

Fire with Alarm

 

Short on sensor loop starts verification process:

 

 

Verification (use Fire

 

1.

Control panel removes power to Point 1 for 4 seconds to reset smoke

 

 

with Alarm Verification

 

 

detectors.

 

 

for Point 1 only)

 

2.

Short on loop within 120 seconds of reset starts alarm response. If the

 

 

 

 

 

 

 

 

 

point remains normal or open for the 120-second verification window

 

 

 

 

 

no alarm response occurs.

 

 

 

 

3.

Verification is not recommended for RF points.

 

 

 

 

4.

Missing Fire points generate a trouble response when the system is on

 

 

 

 

 

or off.

 

 

 

 

5.

RF Tamper for Fire points generates a trouble response when the

 

 

 

 

 

system is on or off.

 

 

 

 

6.

Do not use Fire Alarm Verification points as Cross or Partner points.

 

 

 

 

 

Refer to Section 11.3 Digit 3, Point Options.

 

Bosch Security Systems 7/05 35114F

Page 37
Image 37