Keypad Programming

2000 Series Program Entry Guide 18.0

Keypad Programming

 

 

EN 65

18.0Keypad Programming

18.1Getting Started

Text Keypad Required: You need a text keypad with its address set to 1 connected to the control panel to use keypad programming. You cannot program from an LED keypad. You do not need to leave the text keypad connected to the system after the programming session.

You do not need to reserve an address for a text keypad to use keypad programming. When the standby switch is locked down, the system allows you to use a text keypad with its address set to 1 for keypad programming, even though address 1 can be programmed for another device.

To start keypad programming:

1.Lock the standby switch down. You must connect a text keypad (address set to 1) to the control panel to program. The text keypad can be removed after programming.

2.Press the [1] key on the text keypad.

3.Enter your installer passcode. The default installer passcode is 654321. The default passcode length is three characters, so if you did not change the default entries, press [6][5][4].

The keypad scrolls the installer menu.

4.Press the [8] key to enter keypad programming, View Mode. If you press the [CLEAR] key now, the keypad exits the Programming Mode and returns to the Installer Menu.

18.2View Mode

In View Mode you can view each program prompt. You must enter the Modify Mode to make changes for any prompt. When you first enter View Mode, you are at Group 1, Prompt 1. Figure 2 shows Group 1, Prompt 1, Account Number, with an entry of 1234.

Figure 2: View Mode

1.1

1234

The group and prompt number appear in line 1. For most prompts, the current entry for the prompt is in line 2. The exceptions are the prompts containing phone numbers, Phone 1, Phone 2, and RAM Phone. The first seven characters for these prompts appear on line 1 with the group and prompt numbers. The remaining characters appear on line 2.

Table 20: View Mode Keys

A-Key

Pressing the [A] key while in View Mode

 

enters Modify Mode where you can change

 

the entry for a prompt. Modify Mode is

 

described in the Section 18.3 Modify

 

Mode.

B-Key

Pressing the [B] key in View Mode moves

 

you to the first prompt in the previous

 

group.

 

If you were at 3.2 (group 3, prompt 2),

 

pressing the [B] key moves you to 2.1

 

(Group 2, Prompt 1).

C-Key

Pressing the [C] key in View Mode moves

 

you to the first prompt in the next group.

 

If you were at 3.2 (Group 3, Prompt 2),

 

pressing the [C] key moves you to 4.1

 

(Group 4, Prompt 1).

*-Key

Pressing the [*] key in View Mode moves

 

you to the next prompt in the group.

 

If you are at the last prompt in the group

 

when you press the [*] key the system

 

returns to Prompt 1.