Page 57
Image 57
User Test

2000 Series Program Entry Guide 14.0

User Test

 

 

EN 57

14.0 User Test

If the user presses [1] at the keypad and then enters their passcode, the system performs a user test. Prompts 1 to 3 tell the system what functions to perform for the User Test.

1 User Tst, Bell

Default:

No

 

 

Selection:

Yes, No

 

 

0

No

 

 

1

Yes

 

 

Setting the Usr Tst, Bell prompt to Yes makes a Bell Test part of the User Test. The system activates the Alarm Output (Terminals 4 and 5) for 3 seconds. Light 1 on the keypad flashes for the duration of the test.

Set this prompt to Yes for UL 1023,

Household Fire systems.

3 User Tst, Comm

Default:

 

No

 

 

Selection:

 

 

Yes, No

 

 

 

 

 

 

 

 

 

 

 

0

 

 

No

 

 

 

1

 

Yes

 

 

 

 

 

 

Setting the Usr Tst, Comm prompt to Yes makes a Communication Test part of the User Test. When the user presses [1] and enters a passcode, the system sends a Test Report to the receiver. Light 1 flashes during the test. If the system fails to communicate with the receiver, the system goes into communication failure and displays a system trouble at the keypad by flashing the OK light. Refer to Check System in the User Guide.

The system makes five attempts to send the report if only one phone number is programmed. It makes ten attempts if two numbers are programmed. Refer to Phone 1, Phone 2 , in Section 2.0 Phone.

2 User Tst, Battery

Default:

No

Selection:

Yes, No

 

 

0

No

 

 

1

Yes

 

 

Setting the Usr Tst, Battery prompt to Yes makes a Battery Test part of the User Test. Pressing [1] causes the system to run solely on battery power for 4 minutes. Light 1 flashes while the control panel is on battery power. If the battery voltage falls below 12.1 VDC during that 4 minutes, the system restores AC power and displays a system trouble at the keypad by flashing the OK light. Refer to System Troubles in the User Guide.

The system sends a Low Battery Report to the receiver.

Users can end the test by pressing the [CLEAR] key.

Set this prompt to Yes for UL 1023,

Household Fire systems.

Bosch Security Systems 7/05 35114F