Table 18: Relay Function Selections

Programmers

Keypad

Description

No Output

0

No output at the relay terminal.

Alarm

1

Provides a steady output when a point is in an alarm condition.

 

 

The relay output follows Bell Time.

 

 

Note:

 

 

This output does not occur for alarms caused by A, B, C Keys.

 

 

Entering a combination to acknowledge an alarm resets the relay.

 

 

Select the points to monitor for alarms at the Parameter prompt.

Alarm Memory

2

Provides a steady output when a point shows alarm memory at the keypad.

 

 

Turning the system on clears alarm memory and ends the output. This output

 

 

does not occur for alarms caused by A, B, C Keys.

 

 

Select the points to monitor for alarm memory at the Parameter prompt.

Point Trouble

3

Provides a steady output when selected points are in trouble.

 

 

Select the points to monitor for troubles at the Parameter prompt. Swinger

 

 

bypass is a point trouble and activates the Point Trouble Relay function.

Follow Point

4

Provides a steady output when selected points are faulted (including point trouble

 

 

and alarm).

 

 

Select the points to monitor for faults at the Parameter prompt.

Watch Tone

5

Activates the relay output in parallel to the watch tone for selected points. Refer to

 

 

Key 7, Watch Tone in the User’s Guide. If you set the watch tone to No Tone, the

 

 

Watch Tone relay does not activate. Select the points for Watch Tone monitor at

 

 

the Parameter prompt.

 

 

 

A,B,C Key, Steady

6

Activates the relay output when a user presses a selected function key. The relay

 

 

output remains activated until a user performs a System Reset (presses [3] and

 

 

enters a passcode).

 

 

Select the function keys to monitor at the Parameter prompt.

A,B,C Key, Pulse

7

Activates the relay output when a user presses a selected function key. The relay

 

 

output pulses until a user performs a System Reset (presses [3] and enters a

 

 

passcode).

 

 

Select the function keys to monitor at the Parameter prompt.