2000 Series Program Entry Guide 11.0 | Point Codes |
|
|
EN 39
Table 5: continued
Display | Selection | Description | ||||
| 6 |
|
| Controlled, All, |
| When control panel is All On (armed), short or open starts entry delay if no |
|
|
|
| Delay |
| Trouble option. Refer to Section 11.3 Digit 3, Point Options. |
|
|
|
|
|
| All points must be normal (not faulted) or bypassed before control panel can |
|
|
|
|
|
| be All armed. |
|
|
|
|
|
| If an alarm occurs on these points within 2 minutes of a closing (exit time |
|
|
|
|
|
| expired, Excursion/Exit included), the system sends a RECENT CLOSING |
|
|
|
|
|
| message with the Alarm Report. |
|
|
|
|
|
| If these points are faulted at the end of exit delay, the system waits a period |
|
|
|
|
|
| equal to entry delay before sending an Alarm Report. If the system is not |
|
|
|
|
|
| turned off, it sends an EXIT ERROR message with the Alarm Report. |
|
|
|
|
|
| Missing Controlled points generate an alarm response when on, a trouble |
|
|
|
|
|
| response when off. |
|
|
|
|
|
| RF Tamper for a Controlled point generates an alarm response when on, a |
|
|
|
|
|
| trouble response when off. |
7 |
| Controlled, All, | When the control panel is All On (armed), and entry or exit delay times | |||
|
|
|
| No Delay | expire, a short or open causes an alarm response. These points follow the | |
|
|
|
| (Follower) | entry and exit delay and are ignored when faulted during these time periods. | |
|
|
|
|
|
| All points must be normal (not faulted) or bypassed before the control panel |
|
|
|
|
|
| can be All armed. |
|
|
|
|
|
| If an alarm occurs on these points within 2 minutes of a closing (exit time |
|
|
|
|
|
| expired, Excursion/Exit included), the system sends a RECENT CLOSING |
|
|
|
|
|
| message with the Alarm Report. |
|
|
|
|
|
| If these points are faulted at the end of exit delay, the system waits a period |
|
|
|
|
|
| equal to entry delay before sending an Alarm Report. If the system is not |
|
|
|
|
|
| turned off, it sends an EXIT ERROR message with the Alarm Report. |
|
|
|
|
|
| Missing Controlled points generate an alarm response when on, a trouble |
|
|
|
|
|
| response when off. |
|
|
|
|
|
| RF Tamper for a Controlled point generates an alarm response when on, a |
|
|
|
|
|
| trouble response when off. |
| 8 |
|
| Controlled, Part, Delay |
| When control panel is All or Part On (armed) short or open starts entry |
|
|
|
|
|
| delay if no Trouble option. Refer to Section 11.3 Digit 3, Point Options. |
Part points must be normal (not faulted) or bypassed before control panel can be Part armed.
If an alarm occurs on these points within 2 minutes of a closing (exit time expired, Excursion/Exit included), the system sends a RECENT CLOSING message with the Alarm Report.
If these points are faulted at the end of exit delay, the system waits a period equal to entry delay before sending an Alarm Report. If the system is not turned off, it sends an EXIT ERROR message with the Alarm Report. Missing Controlled points generate an alarm response when on, a trouble response when off.
RF Tamper for a Controlled point generates an alarm response when on, a trouble response when off.
Bosch Security Systems 7/05 35114F