2000 Series Program Entry Guide 13.0 | Relays |
|
|
EN 55
Table 18: continued
Programmers | Keypad | Description |
A,B,C Key, | 8 | Activates the relay output when a user presses a selected function key. The relay |
Momentary |
| output activates for 10 seconds. Do not program both relays for this function, |
|
| doing so might cause inconsistent relay operation. |
|
| Select the function keys to monitor at the Parameter prompt. |
Off with Passcode | 9 | Activates the relay for 10 seconds when a selected user turns the system off with |
|
| a passcode. |
|
| Note: |
|
| Do not program both relays for this function, doing so can cause inconsistent relay |
|
| operation. |
|
| Select the Users to monitor at the Parameter prompt. |
Follow Alarm Output | 10 | Parallels activity at the alarm output (Terminals 4 and 5). |
All On | 11 | Activates the relay at the start of exit delay when the system is All On. The |
|
| output remains activated until the system is turned off. |
|
|
|
Part On | 12 | Activates the relay at the start of exit delay when the system is Part On. The |
|
| output remains activated until the system is turned off. |
Reset | 13 | Activates the relay output when a user presses the [3] key to reset the system. |
|
| The relay output activates for 4 seconds. Do not program both relays for this |
|
| function, doing so might cause inconsistent relay operation. |
AC Failure | 14 | Provides a steady output when the system detects a loss of power at Terminals 1 |
|
| and 2. The driver remains activated until AC power restores. |
Battery Trouble | 15 | Provides a steady output when the system detects a low or missing battery |
|
| condition. The relay remains activated until the battery restores. |
Communication Fail | 16 | Provides a steady output when the system fails to communicate with the receiver |
|
| within ten dialing attempts when two phone numbers are programmed, or five |
|
| dialing attempts when one phone number is programmed. The relay remains |
|
| activated until the system successfully communicates a report to the receiver. |
Communicating | 17 | Activates the relay output when the system seizes the phone line. The relay |
|
| remains activated until the system releases the phone line. |
Ground Start | 18 | Activates the relay output for 900 milliseconds after the system seizes the phone |
|
| line. Use this function to generate dial tone on ground start systems. |
|
| Note: |
|
| Do not program both relays for this function, doing so can cause inconsistent relay |
|
| operation. |
Entry and Exit Delay | 19 | Relay provides a steady output during entry and exit delays. |
Extended Delay | 20 | Relay provides a steady output during extended delay. |
|
| The relay does not activate if you fault an Extended Delay point before you start |
|
| exit delay, or if you bypass the Extended Delay point while you are in exit delay. |
Pulsed Output | 21 | This function provides a continuous pulsed output. |
|
| Do not assign this function to a relay without “anding” it to another function. |
|
| Refer to the Relay 1 Logic 1 and Relay 2 Logic 1 prompts in Section 13.1 Relay |
|
| Function Logic. For example, “anding” this function to the Alarm function results |
|
| in pulsed output for the duration of Bell Time. |
|
| The Pulsed Output does not activate when alarms from A, B, C Keys occur. |
Bosch Security Systems 7/05 35114F