Carrier 48AY020-060, 48EW, 48EY024-068, 48AW, 48EK, 48AK, 48AJ, 48EJ specifications

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 115
Image 115

Tables 46-48 show the input and output channel designations.

Table 46 — I/O Channel Designations Base Module — CV

TERMINAL NO.

ASSIGNMENT

TERMINAL NO.

ASSIGNMENT

T1-2

SPT (CCN) — 10KV Thermistor

T23-25

Compressor 2 Safety — DI (24 vac)

T3-4

STO (CCN) — 10KV Thermistor

T24-25

Outside Air Enthalpy — DI (24 vac)

T5-6

OAT — 5KV Thermistor

T26-27

Economizer Pos. — AO (4-20 mA)

T7-8

SAT — 5KV Thermistor

T28-29

Heat 1 Relay — DO (24 vac)

T9-10

T30-29

Heat 2 Relay — DO (24 vac)

T11-12

SAT Reset — AI (4 to 20 mA)

T31-32

CV Power Exhaust 1/Modulating Power Exhaust — DO (115 vac)

T13-14

IAQ Indoor — AI (4 to 20 mA)

T33-32

CV Power Exhaust 2 — DO (115 vac)

T15-16

IAQ Outdoor — AI (4 to 20 mA)

T34-35

Condenser Fan — DO (115 vac)

T17-25

Y1 or Remote Start/Stop — DI (24 vac)

T36-35

OFC2 — DO (115 vac)

T18-25

Y2 — DI (24 vac)

T37-38

T19-25

W1 — DI (24 vac)

T39-38

T20-25

W2 — DI (24 vac)

K1

Indoor Fan Relay — DO (LV)

T21-25

G — DI (24 vac)

K2

Compr. 1 — DO (HV)

T22-25

Compressor 1 Safety — DI (24 vac)

K3

Compr. 2 — DO (HV)

Table 47 — I/O Channel Designations Base Module — VAV

TERMINAL NO.

ASSIGNMENT

TERMINAL NO.

ASSIGNMENT

T1-2

SPT (CCN) — 10KV Thermistor

T23-25

Compressor 2 Safety — DI (24 vac)

T3-4

RAT — 5KV Thermistor

T24-25

Outside Air Enthalpy — DI (24 vac)

T5-6

OAT — 5KV Thermistor

T26-27

Economizer Pos. — AO (4-20 mA)

T7-8

SAT — 5KV Thermistor

T28-29

Heat 1 Relay - DO (24 v)

T9-10

T30-29

Heat Interlock Relay — DO (24 v)

T11-12

SAT Reset — AI (4 to 20 mA)

T31-32

Modulated Power Exhaust — DO (24 vac)

T13-14

IAQ Indoor — AI (4 to 20 mA)

T33-32

T15-16

IAQ Outdoor — AI (4 to 20 mA)

T34-35

Condenser Fan — DO (115 vac)

T17-25

Remote Start/Stop — DI (24 vac)

T36-35

OFC2 — DO (115 vac)

T18-25

T37-38

Unloader 1 — DO (115 vac)

T19-25

T39-38

Unloader 2 — DO (115 vac)

T20-25

K1

Indoor Fan Relay — DO (LV)

T21-25

K2

Compr. 1 — DO (HV)

T22-25

Compressor 1 Safety — DI (24 vac)

K3

Compr. 2 — DO (HV)

Table 48 — I/O Channel Designations Expansion Module (Field-Installed) — CV and VAV

TERMINAL NO.

ASSIGNMENT

TERMINAL NO.

ASSIGNMENT

T1-2

T23 and TB2-1

Fire — Evacuation — DI (24 vac)

T3-4

T24 and TB2-1

Fire — Smoke Purge — DI (24 vac)

T5-6

T26-27

T7-8

T28-29

T9-10

T30 and TB2-2

Alarm Light Indicator — DO (24 vac)

T11-12

T31

Power Exhaust Fire No. 1 — DO (115 vac)

T13-14

T33

Power Exhaust Fire No. 2 — DO (115 vac)

T15-16

T34

Power Exhaust Fire No. 3 — DO (115 vac)

T17 and TB2-1

Fan Status — DI (24 vac)

T36

Power Exhaust Fire No. 4 — DO (115 vac)

T18 and TB2-1

Filter Status - DI (24 vac)

T37

T19 and TB2-1

Field Applied Status — DI (24 vac)

T39

T20 and TB2-1

Demand Limit — DI (24 vac)

K1

T21 and TB2-1

Fire — Unit Shutdown — DI (24 vac)

K2

T22 and TB2-1

Fire — Pressurization — DI (24 vac)

K3

 

 

 

LEGEND (Tables 46-48)

AI

Analog Input

OAT — Outdoor-Air Temperature

AO

Analog Output

OFC — Outdoor Fan Contactor

CCN —

Carrier Comfort Network RAT — Return-Air Temperature

CV

Constant Volume

SAT — Supply-Air Temperature

DI

Direct Input

SPT — Space Temperature

DO

Direct Output

STO — Space Temperature Offset

HV

High Voltage

T

Terminal

IAQ —

Indoor Air Quality

TB

Terminal Block

KV

Kilo-Ohms

VAV — Variable Air Volume

LV

Low Voltage

 

 

NOTE: All even numbered terminals are negative (–) polarity and all odd numbered terminals are positive (+) polarity.

115

Page 115
Image 115