Carrier 48AK, 48EW, 48EY024-068, 48AW, 48EK Field Gas Piping, 48A,E Series Staged Gas Implementation

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 29
Image 29
Fig. 23 — Field Gas Piping

IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

Fig. 23 — Field Gas Piping

OPTIONAL STAGED GAS UNITS — The staging pattern is selected based on Heat Stage Type (HTSTGTYP). Max Capacity per changes default value is selected based on Capac- ity Maximum Stage (CAPMXSTG). See Table 4.

For complete information and service instructions for Staged Gas Control Units, see Control Operation and Trouble- shooting literature.

Step 8 — Controls Options — The control options that the units can provide are based on the following parame- ters: CV (constant volume) or VAV (variable air volume) oper- ation; stand-alone unit with field-supplied sensors installed (CV or VAV); as a system via Carrier Comfort System (TEMP or VVT® [Variable Volume and Temperature]); optional elec- tronic expansion board installed (CV or VAV); linked to the Carrier Comfort Network; availability of a computer and soft- ware (ComfortWORKS® Building Supervisor, and Service Tool) or remote enhanced display accessory installed to access the base control board; and optional factory-installed staged gas control. See Table 5.

NOTE: Access to the base control board allows unit occu- pancy schedules, unit timeclock, and various set points to be changed from their factory-defined default settings.

Table 4 — 48A,E Series Staged Gas Implementation

NUMBER OF STAGES

 

MODEL NUMBER POSITION

POSITION

HEAT SIZE

3

 

5

6,7,8

HTSTGTYP

CAPMXSTG

 

 

 

 

 

 

 

024

 

 

 

 

 

 

 

028

 

 

 

 

 

 

 

030

 

 

 

 

E

 

S

034

Default=1

Default=20

Low

 

 

 

 

038

 

 

 

 

 

 

 

044

 

 

 

 

 

 

 

048

 

 

 

 

 

 

 

020

 

 

 

 

 

 

 

025

 

 

 

5 stages

 

 

 

027

 

 

 

A

 

S

030

Default=1

Default=20

Low

 

 

 

 

035

 

 

 

 

 

 

 

040

 

 

 

 

 

 

 

050

 

 

 

 

 

 

 

038

 

 

 

 

E

 

T

044

Default=1

Default=20

High

 

 

 

 

048

 

 

 

 

 

 

 

035

 

 

 

 

A

 

T

040

Default=1

Default=20

High

 

 

 

 

050

 

 

 

 

 

 

 

024

 

 

 

 

E

 

T

028

Default=2

Default=15

High

 

 

030

 

 

 

 

 

 

 

7 stages

 

 

 

034

 

 

 

 

 

 

020

 

 

 

 

 

 

 

 

 

 

 

A

 

T

025

Default=2

Default=15

High

 

 

027

 

 

 

 

 

 

 

 

 

 

 

030

 

 

 

 

 

 

 

054

 

 

 

 

E

 

T

058

Default=3

Default=15

High

9 stages

 

064

 

 

 

 

 

 

 

 

 

 

068

 

 

 

 

A

 

T

060

Default=3

Default=15

High

 

 

 

 

054

 

 

 

 

E

 

S

058

Default=4

Default=15

Low

11 stages

 

064

 

 

 

 

 

 

 

 

 

 

068

 

 

 

 

A

 

S

060

Default=4

Default=15

Low

29

Page 29
Image 29
Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AJ, 48EJ Field Gas Piping, 48A,E Series Staged Gas Implementation