Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont)

UNIT SIZE

NOMINAL

VOLTAGE RANGE

COMPRESSOR

OFM

 

IFM

POWER

POWER

No. 1

No. 2

 

EXHAUST

SUPPLY

48AJ,AK,

VOLTAGE

 

 

 

 

 

 

AW,AY

(3 PH, 60 Hz)

Min

Max

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

FLA

MCA

MOCP*

 

 

(total)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

30.8/28.0

129.4/126.6

150/150

 

 

 

 

 

 

 

 

 

 

23.6/23.6

153.0/150.2

175/175

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

39.1

256

39.1

256

2

5.3

15

46.2/42.0

146.6/141.3

175/175

 

(ea)

23.6/23.6

170.2/164.9

200/200

 

 

 

 

 

 

 

 

 

 

20

59.4/54.0

163.1/156.3

200/200

 

 

 

 

 

 

 

 

 

 

23.6/23.6

186.7/179.9

225/225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

14

64.2

80

 

 

 

 

 

 

 

 

 

 

12.6

76.8

90

 

 

 

 

 

 

 

 

 

 

 

 

027

460

414

508

19.9

114

19.9

114

2

2.7

15

21

71.5

90

(ea)

12.6

84.1

100

 

 

 

 

 

 

 

 

 

 

20

27

79.0

100

 

 

 

 

 

 

 

 

 

 

12.6

91.6

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

11

51.8

60

 

 

 

 

 

 

 

 

 

 

12.6

64.4

80

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

16

91

16

91

2

2.4

15

17

58.1

70

 

(ea)

12.6

70.7

80

 

 

 

 

 

 

 

 

 

 

20

22

64.3

80

 

 

 

 

 

 

 

 

 

 

12.6

76.9

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

30.8/28.0

151.9/149.1

200/200

 

 

 

 

 

 

 

 

 

 

23.6/23.6

175.5/172.7

225/225

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

57.1

266

39.1

228

2

5.3

15

46.2/42.0

167.3/163.1

200/200

 

(ea)

23.6/23.6

190.9/186.7

225/225

 

 

 

 

 

 

 

 

 

 

20

59.4/54.0

181.1/175.1

225/225

 

 

 

 

 

 

 

 

 

 

23.6/23.6

204.7/198.7

250/250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

14

71.3

90

 

 

 

 

 

 

 

 

 

 

12.6

83.9

100

 

 

 

 

 

 

 

 

 

 

 

 

030

460

414

508

25.6

120

19.9

114

2

2.7

15

21

78.3

100

(ea)

12.6

90.9

110

 

 

 

 

 

 

 

 

 

 

20

27

84.7

110

 

 

 

 

 

 

 

 

 

 

12.6

97.3

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

11

57.4

70

 

 

 

 

 

 

 

 

 

 

12.6

70.0

90

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

20.5

96

16

91

2

2.4

15

17

63.4

80

 

(ea)

12.6

76.0

90

 

 

 

 

 

 

 

 

 

 

20

22

68.8

90

 

 

 

 

 

 

 

 

 

 

12.6

81.4

100

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

*Fuse or HACR circuit breaker per NEC.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.