Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AJ, 48EJ specifications

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 45
Image 45
Thermostat Wiring (CV Only) — Install a Carrier-approved accessory thermostat assembly (per current price pages) according to the installation instructions included with the ac- cessory or these instructions. Locate the thermostat on a solid interior wall in the conditioned space to sense the average temperature.

TI T2 T3

SEE DETAIL B

DETAIL B

(SENSOR CONNECTION

LOCATION)

 

 

 

 

R Y1 Y2 W1 W2 G C X

 

 

 

 

 

 

 

SEE DETAIL A

 

 

 

 

 

TB3

 

 

 

 

DETAIL A

 

 

 

 

(THERMOSTAT CONNECTION

 

 

 

 

LOCATION)

 

 

 

LEGEND

 

 

 

C

Compressor/Contactor

FU

Fuse

OFC

Outdoor-Fan Contactor

CB

Circuit Breaker

GND

Ground

PEC

Power Exhaust Controller

CCB

Control Circuit Breaker

HR

Heater Relay

PES

Power Exhaust Sequencer

CCN

Carrier Comfort Network

IFC

Indoor-Fan Circuit

PESC

Power Exhaust Sequencer Control-

 

 

 

 

 

ler

CR

Control Relay

IFCB

Indoor-Fan Circuit Breaker

SIO

Serial Input/Output

DIP

Dual In-Line Package

IFR

Indoor-Fan Relay

TB

Terminal Block

EQUIP — Equipment

NEC

National Electrical Code

TRAN

Transformer

Thermostat Wiring (CV Only) — Install a Carrier-approved accessory thermostat assembly (per current price pages) according to the installation instructions included with the ac- cessory or these instructions. Locate the thermostat on a solid interior wall in the conditioned space to sense the average temperature.

Route the thermostat cable or equivalent single leads of colored wire from the subbase terminals to the low-voltage connection as shown on unit label wiring diagram and in Fig. 32.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.

Set heat anticipators to 0.1 for all voltages. Settings may be changed slightly to provide a greater degree of comfort for a particular installation.

Sensor Wiring (CV or VAV) — The temperature sensor is wired into the unit control board. See Fig. 33.

The unit is controlled with a T-55 or T-56 (CV only) zone sensor. Terminal TH (T-56) or T1 (T-55) on the sensor is con- nected to T1 of the base control board. Terminal COM (T-56) or T2 (T-55) on the sensor is connected to T2 on the base con- trol board. If a T-56 set point override sensor is used, the over- ride connection SW on the sensor is connected to T3 on the base control board.

If more than sensor is being used and averaged, sensors must be wired in multiples of 4 or 9. See Fig. 34.

Heat Interlock Relay — VAV units require a field-supplied heat interlock relay (HIR) to drive the air terminal wide open when in heat mode. Heat Interlock relay part number is HN61KK040. See Fig. 35 for HIR wiring.

Remote Field Control — A switch closure across terminals R and W1 on TB-3 will initiate the Occupied mode. This can be done manually as well as through a field-supplied timeclock.

Service Tool, Building Supervisor, and ComfortWORKS® Software — Access to the control board can be achieved through the terminal marked CCN via a 3-wire bus.

IMPORTANT: The default bus address is 0. The default element number is 1. Refer to CCN literature for informa- tion on network addressing or changing CCN communica- tion defaults.

Carrier Comfort Network Interface — The rooftop units can be connected to the CCN. The communication bus wiring is supplied and installed in the field. Wiring consists of shielded, 3-conductor cable with drain wire.

The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each sys- tem element communication connector must be wired to the positive pins of the system element on either side of it, the neg- ative pins must be wired to the negative pins, and the signal pins must be wired to signal ground pins. Wiring connections for CCN should be made at the 3-pin plug (CCN located at the base board). Consult CCN literature for further information.

45

Page 45
Image 45
Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AJ, 48EJ specifications