TABLE 1A

96

NOTES:

1.Connect TRAN1 to H4 for 460 v units. Connect to H3 for 230 v. If 208/230 v units are run with a 208-v power supply, connect to H2.

2.Connect TRAN2 to black lead for 460 v units. Connect to orange lead for 230 v units. If 208/230 v units are run with a 208-v power supply, con- nect to red lead.

3.Circuit breaker must trip amps are equal to or less than 156% FLA for CB1 and CB2. All others are 140%.

4.If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.

5.Compressors and/or fan motors are thermally protected.

6.Three phase motors are protected against pri- mary single phasing conditions.

TABLE 1A

The following compressors have two parallel wires run from TB1 to the compressors.

Compressor

Voltage

Wire

Model

Quantity

 

06D-537

208/230-3-60

2

TABLE 2B

The following fan motors have two

parallel wires run from TB1 to the fan motors.

Indoor

Voltage

Wire

Motor

Quantity

 

20 HP

208/230-3-60

2

Fig. 77 — Typical Power Schematic 48EJ,EK,EW,EY024-034; 208/230-3-60 and 460-3-60