Table 1A — Physical Data — 48AJ,AK,AW,AY Units

UNIT 48AJ,AK,AW,AY

 

 

 

 

020D/E

 

 

 

 

025D/E

 

 

 

 

027D/E

 

 

 

 

030D/E

 

NOMINAL CAPACITY (tons)

 

20

 

 

 

 

25

 

 

 

 

27

 

 

 

 

30

 

 

 

BASE UNIT OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

See Operating Weights Table 2.

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Type (Ckt 1 , Ckt 2)

1...06D328, 1...06D818

 

 

2...06D328

 

 

 

2...06D328

 

1...06D537, 1…06D328

Number of Refrigerant Circuits

 

2

 

 

 

 

2

 

 

 

 

2

 

 

 

 

2

 

 

 

Oil (oz) (Ckt 1 , Ckt 2)

 

 

115, 88

 

 

 

 

 

 

115 ea.

 

 

 

 

115 ea.

 

 

 

 

115 ea.

 

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-22

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1

 

 

25-0

 

 

 

 

25-0

 

 

 

 

29-0

 

 

 

 

27-0

 

 

 

Circuit 2

 

 

31-0

 

 

 

 

25-0

 

 

 

 

28-0

 

 

 

 

29-0

 

 

 

CONDENSER COIL *

 

 

 

 

Cross-Hatched 3/8" Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins

 

Quantity

 

 

1

 

 

 

 

1

 

 

 

 

1

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

 

4...15

 

 

 

 

4...15

 

 

 

 

4...15

 

 

 

 

4...15

 

 

 

Total Face Area (sq ft)

 

 

33.3

 

 

 

 

33.3

 

 

 

 

33.3

 

 

 

 

33.3

 

 

 

CONDENSER FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Propeller Type

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Cfm

 

 

13,420

 

 

 

 

13,420

 

 

 

 

13,420

 

 

 

 

13,420

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Diameter (in.)

 

 

2...30

 

 

 

 

2...30

 

 

 

 

2...30

 

 

 

 

2...30

 

 

 

Motor Hp

 

 

1

 

 

 

 

1

 

 

 

 

1

 

 

 

 

1

 

 

 

EVAPORATOR COIL

 

 

 

 

 

 

 

 

 

Cross-Hatched Copper Tubes, Aluminum Plate Fins

 

 

 

 

 

 

 

 

Tube Size (in.)

 

 

3/8

 

 

 

 

3/8

 

 

 

 

3/8

 

 

 

 

3/8

 

 

 

Rows...Fins/in.

 

 

4...15

 

 

 

 

4...15

 

 

 

 

4...15

 

 

 

 

4... 5

 

 

 

Total Face Area (sq ft)

 

 

31.7

 

 

 

 

31.7

 

 

 

 

34.7

 

 

 

 

34.7

 

 

 

EVAPORATOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Centrifugal Type

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

 

 

2...20 X 15

 

 

2... 20 X 15

 

 

2... 20 X 15

 

 

2... 20 X 15

 

 

 

 

 

 

 

 

 

 

 

Type Drive

 

 

 

 

Belt

 

 

 

 

Belt

 

 

 

 

Belt

 

 

 

 

Belt

 

Nominal Cfm

 

 

8,000

 

 

 

 

10,000

 

 

 

 

11,000

 

 

 

 

12,000

 

 

 

Motor Hp

 

5

 

 

10

 

 

15

7.5

 

 

10

 

 

15

10

 

 

15

 

 

20

10

 

 

15

 

 

20

 

 

 

 

 

 

 

 

 

Motor Frame Size

 

184T

 

 

215T

 

 

254T

213T

 

 

215T

 

 

254T

215T

 

 

254T

 

 

256T

215T

 

 

254T

 

 

256T

Motor Bearing Type

 

 

 

 

Ball

 

 

 

 

 

 

Ball

 

 

 

 

 

 

Ball

 

 

 

 

 

 

Ball

 

 

 

Maximum Allowable Rpm

 

 

1200

 

 

 

 

1200

 

 

 

 

1200

 

 

 

 

1200

 

 

 

Motor Pulley Pitch Diameter

4.9

 

 

4.4

 

 

5.7

5.4

 

 

6.1

 

 

5.5

4.4

 

 

4.9

 

 

5.9

4.4

 

 

5.7

 

 

5.9

 

 

 

 

 

 

 

 

Nominal Motor Shaft Diameter (in.)

11/8

 

 

13/8

 

 

13/8

13/8

 

 

13/8

 

 

15/8

13/8

 

 

15/8

 

 

15/8

13/8

 

 

15/8

 

 

15/8

Fan Pulley Pitch Diameter (in.)

12.4

 

 

8.6

 

 

9.1

12.4

 

 

11.1

 

 

8.7

9.4

 

 

8.1

 

 

8.7

9.0

 

 

9.1

 

 

8.7

Nominal Fan Shaft Diameter (in.)

 

 

 

115/16

 

 

 

 

 

 

115/16

 

 

 

 

 

 

115/16

 

 

 

 

 

 

115/16

 

 

 

Belt Quantity

 

1

 

 

2

 

 

2

1

 

 

1

 

 

2

2

 

 

2

 

 

2

2

 

 

2

 

 

2

 

 

 

 

 

 

 

 

 

Belt Type

 

BX56

 

 

BX50

 

 

5VX530

BX56

 

 

5VX590

 

 

5VX570

BX50

 

 

5VX500

 

 

5VX530

BX50

 

 

5VX530

 

 

5VX530

Belt Length (in.)

 

56

 

 

63

 

 

53

56

 

 

59

 

 

57

50

 

 

50

 

 

53

50

 

 

53

 

 

53

Pulley Center Line Distance (in.)

16.0-18.7

 

15.6-18.4

 

15.0-17.9

15.6-18.4

 

15.6-18.4

 

15.0-17.9

15.6-18.4

 

15.0-17.9

 

15.0-17.9

15.6-18.4

 

15.0-17.9

 

15.0-17.9

Factory Speed Setting (rpm)

717

 

 

924

 

 

1096

773

 

 

962

 

 

1106

848

 

 

1059

 

 

1187

884

 

 

1096

 

 

1187

FURNACE SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rollout Switch Cutout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F) †

 

 

225

 

 

 

 

225

 

 

 

 

225

 

 

 

 

225

 

 

 

Burner Orifice Diameter

(in. ...drill size)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

Std

 

.111...34

 

 

 

 

.111...34

 

 

 

 

.111...34

 

 

 

 

.111...34

 

 

 

Liquid Propane

Alt

 

.089...43

 

 

 

 

.089...43

 

 

 

 

.089...43

 

 

 

 

.089...43

 

 

 

Thermostat Heat Anticipator Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 1 (amps)

 

 

0.1

 

 

 

 

0.1

 

 

 

 

0.1

 

 

 

 

0.1

 

 

 

Stage 2 (amps)

 

 

0.1

 

 

 

 

0.1

 

 

 

 

0.1

 

 

 

 

0.1

 

 

 

Gas Input (Btuh)

Stage 1

 

262,500/394,000

 

262,500/394,000

 

262,500/394,000

 

262,500/394,000

 

Stage 2

 

350,000/525,000

 

350,000/525,000

 

350,000/525,000

 

350,000/525,000

Efficiency (Steady State) (%)

 

82

 

 

 

 

82

 

 

 

 

82

 

 

 

 

82

 

 

 

Temperature Rise Range

 

 

15-45/35-65

 

 

 

 

15-45/35-65

 

 

 

 

15-45/35-65

 

 

 

 

15-45/35-65

 

 

 

Manifold Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

Std

 

3.5

 

 

 

 

3.5

 

 

 

 

3.5

 

 

 

 

3.5

 

 

 

Liquid Propane

Alt

 

3.5

 

 

 

 

3.5

 

 

 

 

3.5

 

 

 

 

3.5

 

 

 

Gas Valve Quantity

 

 

2

 

 

 

 

2

 

 

 

 

2

 

 

 

 

2

 

 

 

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

426

 

 

 

 

426

 

 

 

 

426

 

 

 

 

426

 

 

 

Reset (Auto.)

 

 

320

 

 

 

 

320

 

 

 

 

320

 

 

 

 

320

 

 

 

LOW-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

27

 

 

 

 

27

 

 

 

 

27

 

 

 

 

27

 

 

 

Reset (Auto.)

 

 

67

 

 

 

 

67

 

 

 

 

67

 

 

 

 

67

 

 

 

RETURN-AIR FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

 

10...20 x 24 x 2

 

 

10...20 x 24 x 2

 

 

10...20 x 24 x 2

 

 

10...20 x 24 x 2

 

OUTDOOR AIR FILTERS

 

 

 

 

8...16 x 25

 

 

 

 

8...16 x 25

 

 

 

 

8...16 x 25

 

 

 

 

8...16 x 25

 

Quantity...Size (in.)

 

 

 

 

4...20 x 25

 

 

 

 

4...20 x 25

 

 

 

 

4..20 x 25

 

 

 

 

4...20 x 25

 

 

 

LEGEND

Al

Aluminum

Bhp

Brake Horsepower

Cu

Copper

*Sizes 020-030: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion.

Sizes 035-050: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.

†Rollout switch is manual reset.

NOTE: High heat is for 48AJ,AW only.

21

Page 21
Image 21
Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48EJ Physical Data 48AJ,AK,AW,AY Units, Unit 48AJ,AK,AW,AY

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.