Power Failure — The economizer damper motor is a spring return design. In event of power failure, dampers will re- turn to fully closed position until power is restored.

Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Tables 1A and 1B. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures.

Unit panels must be in place when unit is operating during charging procedure.

NOTE: Do not use recycled refrigerant as it may contain contaminants.

NO CHARGE — Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refriger- ant (refer to Tables 1A and 1B).

LOW CHARGE COOLING — Using appropriate cooling charging chart (see Fig. 71-74), add or remove refrigerant until conditions of the appropriate chart are met. Note that charging chart is different from those normally used. An accurate pres- sure gage and temperature sensing device are required. Mea- sure liquid line pressure at the liquid line service valve using pressure gage. Connect temperature sensing device to the liq- uid line near the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading.

Using the above temperature and pressure readings, find the intersect point on the appropriate cooling charging chart. If in- tersection point on chart is above line, add refrigerant. If inter- section point on chart is below line, carefully reclaim some of the charge. Recheck suction pressure as charge is adjusted.

NOTE: Indoor-air cfm must be within normal operating range of unit. All outdoor fans must be operating.

Thermostatic Expansion Valve (TXV) — Each circuit has a TXV. The TXV is nonadjustable and is factory set to main- tain 10 to 13° F superheat leaving the evaporator coil. The TXV controls flow of liquid refrigerant to the evaporator coils.

Gas Valve Adjustment

NATURAL GAS — The 2-stage gas valve opens and closes in response to the thermostat or limit control.

When power is supplied to valve terminals 3 and 4, the pilot valve opens to the preset position. When power is supplied to terminals 1 and 2, the main valve opens to its preset position.

The regular factory setting is stamped on the valve body (3.5 in. wg).

To adjust regulator:

1.Set thermostat at setting for no call for heat.

2.Turn main gas valve to OFF position.

3.Remove 1/8-in. pipe plug from manifold. Install a water manometer pressure-measuring device.

4.Set main gas valve to ON position.

5.Set thermostat at setting to call for heat (high fire).

6.Remove screw cap covering regulator adjustment screw (See Fig. 75).

7.Turn adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure.

8.Once desired pressure is established, set unit to no call for heat (3.3-in. wg high fire).

9.Turn main gas valve to OFF position.

10.Remove pressure-measuring device and replace 1/8-in. pipe plug and screw cap.

11.Turn main gas valve to ON position and check heating operation.

Fig. 71 — Cooling Charging Chart,

48EJ,EK,EW,EY024-034

Fig. 72 — Cooling Charging Chart,

48EJ,EK,EW,EY038-048

93

Page 93
Image 93
Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK Gas Valve Adjustment, Cooling Charging Chart 48EJ,EK,EW,EY024-034

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.