Carrier 48EY024-068, 48EW, 48AW, 48AY020-060, 48EK Field Modifications, Side Return Air Conversion

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 57
Image 57
Step 13 — Field Modifications

Step 13 — Field Modifications

DUCTWORK

Bottom Return Units (48AJ,AK,EJ,EK) Field-Modified for Side Return — 48AJ,AK and 48EJ,EK units with bottom re- turn air connections may be field-modified to accommodate side return air connections.

IMPORTANT: The following section is a guideline and not a comprehensive procedure to field modify the units. The installing contractor must provide some design initiative. Field-conversion is complex and is not recommended. Units with electric heat must not be converted because of potential heating mode operating problems.

Conversion to horizontal return requires that the bottom re- turn openings of the unit must be sealed with airtight panels ca- pable of supporting the weight of a person. The return duct- work connection locations on the side of the unit are higher than normal (31-in. high). Unit-mounted power exhaust or barometric relief cannot be used because of return air ductwork will cover the power exhaust or barometric relief installation locations. Power exhaust or barometric relief may be installed in the return air ductwork.

To convert the unit, perform the following:

1.Seal the bottom return openings of the unit with airtight panels capable of supporting the weight of a person.

2.Remove the panels located below the economizer out- door air dampers. These openings will be used for the re- turn air ductwork. There are 2 panels on 48AJ,AK020- 050 and 48EJ,EK024-048 units. There are 3 panels on

48AJ,AK060 and 48EJ,EK054-068 units. These open- ings are normally used for power exhaust or barometric relief.

3.Run the return air ductwork up to the openings. One sin- gle duct is recommended to connect to the unit over the return air openings. See Fig. 54. The return duct must in- corporate a minimum 3/4-in. flange for connection to the unit cabinet. The unit does not have duct flanges for this conversion.

Side Supply and Return Units (48AW,AY,EW,EY) With Field-Installed Power Exhaust in Return Duct — Space must be available in the return duct to mount the power exhaust fan (gravity relief) modules. Dimensions and suggested locations are shown in Fig. 55. These instructions are a guideline and not a comprehensive procedure. The design contractor must pro- vide some design initiative.

The wiring harness that is provided with the power exhaust accessory is not long enough for the fan modules to be mount- ed in the return air duct. Field-supplied wiring must be spliced into the harness. Use a junction box at each splice. The wiring may be run in the return duct as shown in Fig. 55, or externally in conduit. A service access panel will be needed near each power exhaust fan.

ELECTRIC UNLOADERS (Constant Volume Units Only) — The rooftop units with version 4.0 control software and later are capable of controlling electronic unloaders when in the constant volume (CV) operating mode. The unloaders may be installed in the field and wired to the control box as shown in Fig. 56.

97.78” (020-050)(024-048), 150.47” (060)(054-068)

INSIDE DIMENSION

RA

31.25”

 

INSIDE

Fig. 54 — Side Return Air Conversion

57

Page 57
Image 57
Carrier 48EY024-068, 48EW, 48AW, 48AY020-060, 48EK, 48AK, 48AJ, 48EJ Field Modifications, Side Return Air Conversion