Carrier 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48AJ, 48EJ DIP Switch Configuration

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 64
Image 64
Table 17 — DIP Switch Configuration

DIP switch 6 configures the Time Guard® override and, when used with the field test function, sets the minimum damper position

DIP switch 7 configures the unit for gas heat or electric heat

DIP switch 8 configures the unit for heat pump or air conditioner operation.

Crankcase Heater — Units are equipped with crank- case heaters. Crankcase heaters are energized as long as there is power supplied to unit. Crankcase heaters deenergize while compressors are running.

IMPORTANT: To prevent damage to compressors, crank- case heater should be energized 24-hours prior to start-up.

Evaporator Fan — Fan belt and fixed pulleys are factory-installed. See Tables 19-33 for fan performance and motor limitations data. Remove tape from fan pulley, and be sure that fans rotate in the proper direction. See Table 34 for air

quantity limits. Static pressure drop for power exhaust is negli- gible. To alter fan performance, see Evaporator Fan Perfor- mance Adjustment section on page 91.

Condenser Fans and Motors — Condenser fans and motors are factory set. Refer to Condenser-Fan Adjustment section on page 92 as required. Be sure that fans rotate in the proper direction. Fan no. 2 (48AJ,AK,AW,AY020-030 and 48EJ,EK,EW,EY024-034), fans no. 3 and 4 (48AJ,AK,AW, AY035-050 and 48EJ,EK,EW,EY038-054), and fans no. 4, 5, and 6 (48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY058-068) are cycled on the outdoor-air temperature.

The VFD will always provide the proper phase sequence to the indoor-fan motor to operate in the proper rotation regard- less of the phase sequence to the unit. If on start-up, the outdoor fans operate backwards but the indoor fan operates in the cor- rect direction, reverse any two leads to the unit main terminal block and all fans will operate in the correct direction.

Table 16A — Power Exhaust Default Set Points (48AJ,AK,AW,AY020-050 and 48EJ,EK,EW,EY024-048)

STAGE

OFFSET

DIFFERENTIAL

OFF VOLTAGE

ON VOLTAGE

OFF STATIC PRESSURE

(in.wg)

 

 

 

 

 

1

50%

3%

6.0

6.3

0.00

2

55%

3%

6.5

6.8

0.06

3

60%

3%

7.0

7.3

0.12

4

64%

3%

7.4

7.7

0.18

Table 16B — Power Exhaust Default Set Points (48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068)

STAGE

OFFSET

DIFFERENTIAL

OFF VOLTAGE

ON VOLTAGE

OFF STATIC PRESSURE

(in.wg)

 

 

 

 

 

1

50%

3%

6.0

6.3

0.00

2

55%

3%

6.5

6.8

0.06

3

60%

3%

7.0

7.3

0.12

4

65%

3%

7.5

7.8

0.19

5

70%

3%

8.0

8.3

0.25

6

75%

3%

8.5

8.8

0.31

Table 17 — DIP Switch Configuration

SETTING

1

2

3

4

5

6

7

8

 

 

 

 

 

VAV —

 

 

 

 

 

VAV — Space Sensor

 

 

Occupied

Time Guard® Override

 

 

 

 

Installed

 

 

Heat

ON

 

 

OPEN

VAV

 

Expansion

Field Test

Enabled

 

Gas Heat

Heat Pump

 

Board

ON

CV —

IN CONJUNCTION

Operation

 

 

 

 

 

 

CV — CCN or Sensors

 

 

Modulated

WITH FIELD TEST

 

 

 

 

Used

 

 

Power

— Set Minimum

 

 

 

 

 

 

 

Exhaust

Damper Position

 

 

 

 

 

 

 

VAV —

 

 

 

 

 

VAV — No Space Sensor

 

 

Occupied

 

 

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Control

Field Test

Disabled

Time Guard Override

 

Air Conditioner

CLOSED

CV

 

CV —

Electric Heat

 

Board Only

OFF

OFF

Operation

 

 

 

Constant

 

 

 

 

 

 

 

 

 

 

 

CV — Thermostat

 

 

Volume

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

Exhaust

 

 

 

LEGEND

CCN — Carrier Comfort Network

CV — Constant Volume

VAV — Variable Air Volume

NOTES:

1.The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is OPEN.

2.The configuration of DIP switches 2 and 5 are dependent on DIP switch 1. If DIP switch 1 is set to OPEN (VAV operation), then DIP switches 2 and 5 will configure VAV functions.

3.When the unit is field-tested (DIP switch 4 to OPEN), the func- tion of DIP switch 6 changes and it is used to set the minimum damper position.

4.Recycle power to unit after modifying DIP switches. This will allow the unit to access the new configurations and update its tables.

64

Page 64
Image 64
Carrier 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48AJ, 48EJ specifications DIP Switch Configuration