Carrier 48AJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48EJ Thermistor Designations

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 30
Image 30
Table 6 — Thermistor Designations

Table 5 — Controls Options and Configurations (Non-Thermostat Applications)

 

UNIT CONFIGURATION

DEFAULT COOLING

DEFAULT HEATING

CV or VAV Unit with SPT Sensor

Unoccupied Cooling — 90 F (32 C) (SPT)

Unoccupied Heating — 55 F (13 C) (SPT)

Occupied Cooling — NA

Occupied Heating — NA

 

 

CV Unit with SPT Sensor and Remote

Unoccupied Cooling — 90 F (32 C) (SPT)

Unoccupied Heating — 55 F (13 C) (SPT)

Start/Stop Switch

Occupied Cooling — 78 F (26 C) (SPT)

Occupied Heating — 68 F (20 C) (SPT)

VAV Unit Remote Start/Stop Switch Only

Unoccupied Cooling — 90 F (32 C)(SPT)

Unoccupied Heating — 55 F (13 C) (RAT)

Occupied Cooling — 55 F (13 C) SPT)

Occupied Heating — 68 F (20 C) (RAT)*

 

 

VAV Unit with SPT Sensor and Remote

Unoccupied Cooling — 90 F (32 C) (SPT)

Unoccupied Heating — 55 F (13C) (SPT)

Start/Stop Switch

Occupied Cooling — 55 F (13 C) (SAT)

Occupied Heating — 68 F (20 C) (RAT)*

 

LEGEND

 

 

CV

Constant Volume

 

 

NA

Not Available

 

 

RAT — Return-Air Temperature

 

 

SAT — Supply-Air Temperature

 

 

SPT

Space Temperature

 

 

VAV

Variable Air Volume

 

 

*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled).

NOTE: Space temperature sensor and remote start/stop switch are field-supplied.

STAGED GAS UNIT APPLICATIONS — The rooftop units may be ordered with an optional factory-installed staged gas control system that monitors heating operation of the rooftop unit.

IMPORTANT: An accessory field-supplied Navigator dis- play module is required for all staged gas control units.

Install Supply-Air Thermistors (Staged Gas Units Only)Supply-air thermistors are a field-installed factory-provided component. Three supply-air thermistors are shipped with staged gas units and are inside the heating section. Thermistor wires must be connected to SGC (staged gas controller) in the heating section. See Table 6 and Fig 24. The supply-air ther- mistors should be located in the supply duct with the following criteria:

downstream of the heat exchanger cells

equally spaced as far as possible from the heat exchanger cells

a duct location where none of the supply air thermistors are within sight of the heat exchanger cells

a duct location with good mixed supply air portion of the unit.

THERMISTORS — All units are equipped with a supply air thermistor (SAT) located in the supply fan discharge and an outdoor air thermistor (OAT) located in the outdoor air hood. Variable air volume (VAV) units are supplied with a return air thermistor (RAT) located on the return air damper support.

CONSTANT VOLUME APPLICATIONS — The units, as shipped, are operable as stand-alone units, using either a stan- dard (mechanical or electronic) 2-stage heat, 2-stage cool ther- mostat, or with an electronic room sensor and a timeclock to establish unit start and stop times.

With a standard thermostat (programmable is optional), heating and cooling operation is set by space temperature.

With a space sensor and timeclock, the machine will operate at default values unless they are changed using appropriate in- put devices. The space sensor senses space temperature and may be equipped with a timed override feature, which allows unit operation during unoccupied periods.

The space sensors may be used in multiples of 4 or 9 to achieve space temperature averaging. The use of a space sensor also allows the unit to be turned on and off from a remote signal.

 

 

Table 6 — Thermistor Designations

 

 

 

 

 

 

PIN

FUNCTION AND LOCATION

 

THERMISTOR

CONNECTION

 

PART NO.

Thermistors

 

POINT

 

 

 

 

SAT 1

J8 – 1,2 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section

 

underneath the gas heat section (factory-provided, field-installed)

 

 

 

 

SAT 2

J8 – 3,4 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section

HH79NZ016

underneath the gas heat section (factory-provided, field-installed)

 

 

 

SAT 3

J8 – 5,6 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section

 

underneath the gas heat section (factory-provided, field-installed)

 

 

 

 

30

Page 30
Image 30
Carrier 48AJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48EJ specifications Thermistor Designations