Carrier 48EJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48AJ Supply-AirThermistor Connections

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 31
Image 31
Fig. 24 — Supply-Air Thermistor Connections

Fig. 24 — Supply-Air Thermistor Connections

Features with Thermostat Control of Unit

two-stage heating

two-stage cooling

control of unit using Y1, Y2, W1, W2, and G thermostat inputs

control of the indoor fan

outdoor-air temperature/supply-air temperature monitoring

control of an outdoor air condenser fan based on out- door-air temperature

control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using supply-air temperature as a control point

control of the economizer damper and indoor fan to obtain unoccupied free cooling

provide power exhaust output to an external power exhaust controller

support a field test for field checkout

control of 2 stages of CV power exhaust

compressor Time Guard® (power up, minimum off and on times)

compressor lockout during low supply-air temperature

Additional features are provided by accessing the standard unit control board via software with a computer. These features are:

electronic expansion board features (if installed)

control board diagnostics

ability to change supply air set point (economizer control)

ability to change high outdoor temperature lockout set point (economizer control)

ability to change power exhaust set points

NOTE: A CV unit without a thermostat requires a field- supplied sensor for operation.

Features with Sensor Control of Unit (Stand-Alone Applica- tions — Unit control is limited to CV unoccupied default set points, 90 F for cooling, 55 F for heating unless a computer has been used to change the set points. There are 2 sensor options available:

T-55 sensor will monitor room temperature and provide unoccupied override capability (1 hour)

T-56 sensor will monitor room temperature, provide unoccupied override capability (1 hour), and provide a temperature offset of 5° F.

Standard features are:

support of remote occupied/unoccupied input to start and stop the unit

cooling capacity control of 3 stages using economizer and 2 compressors to maintain space temperature to an occupied or unoccupied set point

enable heating or cooling during unoccupied periods as required to maintain space temperature within the unoc- cupied set points

adjustment of space temperature set points of ±5° F when using a T-56 sensor

provides CCN (Carrier Comfort Network) IAQ (Indoor- Air Quality) participation

control of modulating economizer damper to maintain indoor air quality (IAQ) when outdoor conditions are suitable (this function is provided in the base unit con- trols on units with serial number 0600F or later)

NOTE: The IAQ sensor must be set for current output (4 to 20 mA), not voltage output. Ensure the jumper on the sensor is in the upper position. See Fig. 25.

Additional features with sensor control of unit (with com- puter access or Remote Enhanced Display) are:

365-day timeclock with backup (supports minute, hour, day of week, date, month, and year)

daylight savings time function

occupancy control with 8 periods for unit operation

holiday table containing up to 18 holiday schedules

ability to initiate timed override from T-55 or T-56 sen- sors for a timed period of 1 to 4 hours

ability to use multiple space temperature sensors to aver- age the space temperature

supply-air temperature reset for the supply-air tempera- ture set point

temperature compensated start to calculate early start times before occupancy

access to the Display, Maintenance, Configuration, Ser- vice, and Set Point data tables through network software

loadshed and demand limiting

When the unit is equipped with a field-supplied space tem- perature sensor and a remote contact closure (remote start/ stop) on the base control board, the occupied default set points will monitor unit operation. The occupied default set points are 78 F cooling and 68 F heating (if heating is present). See Fig. 26 for remote start/stop wiring.

NOTE: For units with a field-supplied space temperature sen- sor which have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/ stop closure will allow the unit to operate in the pre-configured occupied default set points of 78 F cooling and 68 F heating. Without this feature, the unit will control to the unoccupied default set points of 90 F cooling and 55 F heating.

31

Page 31
Image 31
Carrier 48EJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48AJ specifications Supply-AirThermistor Connections