Fig. 24 — Supply-Air Thermistor Connections
Features with Thermostat Control of Unit
•
•
•control of unit using Y1, Y2, W1, W2, and G thermostat inputs
•control of the indoor fan
•
•control of an outdoor air condenser fan based on out-
•control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using
•control of the economizer damper and indoor fan to obtain unoccupied free cooling
•provide power exhaust output to an external power exhaust controller
•support a field test for field checkout
•control of 2 stages of CV power exhaust
•compressor Time Guard® (power up, minimum off and on times)
•compressor lockout during low
Additional features are provided by accessing the standard unit control board via software with a computer. These features are:
•electronic expansion board features (if installed)
•control board diagnostics
•ability to change supply air set point (economizer control)
•ability to change high outdoor temperature lockout set point (economizer control)
•ability to change power exhaust set points
NOTE: A CV unit without a thermostat requires a field- supplied sensor for operation.
Features with Sensor Control of Unit
•
•
Standard features are:
•support of remote occupied/unoccupied input to start and stop the unit
•cooling capacity control of 3 stages using economizer and 2 compressors to maintain space temperature to an occupied or unoccupied set point
•enable heating or cooling during unoccupied periods as required to maintain space temperature within the unoc- cupied set points
•adjustment of space temperature set points of ±5° F when using a
•provides CCN (Carrier Comfort Network) IAQ (Indoor- Air Quality) participation
•control of modulating economizer damper to maintain indoor air quality (IAQ) when outdoor conditions are suitable (this function is provided in the base unit con- trols on units with serial number 0600F or later)
NOTE: The IAQ sensor must be set for current output (4 to 20 mA), not voltage output. Ensure the jumper on the sensor is in the upper position. See Fig. 25.
Additional features with sensor control of unit (with com- puter access or Remote Enhanced Display) are:
•
•daylight savings time function
•occupancy control with 8 periods for unit operation
•holiday table containing up to 18 holiday schedules
•ability to initiate timed override from
•ability to use multiple space temperature sensors to aver- age the space temperature
•
•temperature compensated start to calculate early start times before occupancy
•access to the Display, Maintenance, Configuration, Ser- vice, and Set Point data tables through network software
•loadshed and demand limiting
When the unit is equipped with a
NOTE: For units with a
31